| 2017-11-14 07:55:15 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16120363 |
| | 11/14/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | SOME OF THE COMMENTS FROM THE 1ST REVIEW WERE ADDRESSED |
| | AND STILL EXIST. I HAVE REPRINTED THOSE COMMENTS BELOW |
| | WITH ADDITIONAL REMARKS BASED ON THE NARRATIVE RESPONSE |
| | FROM KAMM ENGINEERING |
| | |
| | 2) S-2: REFER TO TABLE 1509.6.5 FBC-14 BUILDING: |
| | MINIMUM 48 INCHES CLEARANCE DISTANCE REQUIRED BELOW THE |
| | NEW TOWER. (KAMM'S RESPONSE- "TO BE PROVIDED BY |
| | STRUCTURAL ENGINEER"). |
| | |
| | 4) PROVIDE DETAILS AND DRAWINGS FOR THE ACCESS LADDER |
| | AND SERVICE PLATFORM- SEE SECTIONS 304.11, 306.1, & |
| | 306.5. *(KAMM'S RESPONSE- "NOT REQUIRED PER |
| | MANUFACTURER'S DRAWINGS".) |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TOWER. |
| | (KAMM'S RESPONSE- "TO BE PROVIDED BY THE CONTRACTOR"). |
| | |
| | 6) COMMISSIONING OF THE SYSTEM IS REQUIRED IN |
| | ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY |
| | CONSERVATION. PLEASE SUBMIT A COMMISSIONING PLAN IN |
| | COMPLIANCE WITH SECTION C408.2.1. (KAMM'S RESPONSE- |
| | "COMMISSIONING IS NOT REQUIRED PER SECTION C101.4.8 |
| | FBC-14 ENERGY CONSERVATION"). IT IS AGREED THAT THE |
| | BUILDING IS EXEMPT, HOWEVER THE NEW COOLING TOWER, |
| | PUMPS, TREATMENT |
| | |
| | SYSTEM, AND NEW PIPINGS MUST BE TESTED TO VERIFY WATER |
| | TEMPERATURES AND FLOWS ARE PER PLAN AND SPECIFICATIONS. |
| | PLEASE PROVIDE A NARRATIVE CLARIFYING WHAT TESTING WILL |
| | BE PERFORMED ON THE NEW EQUIPMENT- SECTION C408.2 |
| | MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION |
| | REQUIREMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |