| Plan Review Notes For Permit 16120363 |
| Permit Number |
16120363 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-19 09:03:44 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16120363 | | | 12/19/16 | | | | | | 1) SHEETS S-2 & M6.1: DIMENSIONS OF THE TOWER DON'T | | | MATCH. | | | | | | 2) S-2: REFER TO TABLE 1509.6.5 FBC-14 BUILDING: | | | MINIMUM 48 INCHES CLEARANCE DISTANCE REQUIRED BELOW THE | | | NEW TOWER. | | | | | | 3) PROVIDE PIPING AND PIPE INSULATION SPECIFICATIONS. | | | | | | 4) PROVIDE DETAILS AND DTRAWINGS FOR THE ACCESS LADDER | | | AND SERVICE PLATFORM- SEE SECTIONS 304.11, 306.1, & | | | 306.5 | | | | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TOWER. | | | | | | 6) COMMISSIONING OF THE SYSTEM IS REQUIRED IN | | | ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY | | | CONSERVATION. PLEASE SUBMIT A COMMISSIONING PLAN IN | | | COMPLIANCE WITH SECTION C408.2.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|