| Plan Review Notes For Permit 16120356 |
| Permit Number |
16120356 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-03 11:55:41 | | | | 16120356 | | | 1021 AVON ROAD | | | SF RENOVATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | THE NOTES ON THE PLANS REQUIRE SOME CLARIFICATION. THEY | | | REFER TO SUB PANELS AND NEW PANELS WHICH ARE NOT SHOWN. | | | THE NOTES REFER TO A CARBON MONOXIDE (CO) DETECTOR BUT | | | THE PLANS ONLY SHOW SMOKE DETECTORS. ARE THERE GAS | | | APPLIANCES ON THIS JOB? | | | | | | IS THIS A NEW SERVICE OR AN EXISTING SERVICE? THE LOAD | | | CALCULATION SHOWS A 200 AMP MAIN BREAKER PANEL BUT THE | | | RISER AND PANEL SCHEDULE ARE SHOWING SOMETHING | | | DIFFERENT. | | | | | | PROVIDE A DETAIL FOR THE EXISTING ELECTRICAL SERVICE | | | MAST WHERE IT PENETRATES THE NEW ALUMINUM CANOPY TO | | | CONNECT TO THE OVERHEAD SERVICE CONDUCTORS. THERE ARE | | | SOME SAFETY CLEARANCES IN THE ELECTRICAL CODE THAT NEED | | | TO BE FOLLOWED. NEC 230.24 | | | | | | ARC FAULT CIRCUITS ARE NOT LIMITED TO BEDROOMS ONLY. | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH | | | CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12 | | | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94; FBC R E3609 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654(OFFICE) | | | 561-373-3701(CELL) | | | | | | | | | |
|