2017-01-03 11:55:41 
 16120356
 1021 AVON ROAD
 SF RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE NOTES ON THE PLANS REQUIRE SOME CLARIFICATION. THEY
 REFER TO SUB PANELS AND NEW PANELS WHICH ARE NOT SHOWN.
 THE NOTES REFER TO A CARBON MONOXIDE (CO) DETECTOR BUT
 THE PLANS ONLY SHOW SMOKE DETECTORS. ARE THERE GAS
 APPLIANCES ON THIS JOB?
  
 IS THIS A NEW SERVICE OR AN EXISTING SERVICE? THE LOAD
 CALCULATION SHOWS A 200 AMP MAIN BREAKER PANEL BUT THE
 RISER AND PANEL SCHEDULE ARE SHOWING SOMETHING
 DIFFERENT.
  
 PROVIDE A DETAIL FOR THE EXISTING ELECTRICAL SERVICE
 MAST WHERE IT PENETRATES THE NEW ALUMINUM CANOPY TO
 CONNECT TO THE OVERHEAD SERVICE CONDUCTORS. THERE ARE
 SOME SAFETY CLEARANCES IN THE ELECTRICAL CODE THAT NEED
 TO BE FOLLOWED. NEC 230.24
  
 ARC FAULT CIRCUITS ARE NOT LIMITED TO BEDROOMS ONLY.
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
  