| 2017-01-11 17:40:42 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) NEW SKYLIGHT AS SHOWN ON PLANS. |
| | |
| | B) SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| | |
| | C) ROOF TILE AS SPECIFIED ON THE PERMIT APPLICATION. |
| | NOTE: CLARIFY SCOPE OF WORK FOR NEW ROOFING. |
| | |
| | D) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| | RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED |
| | ADHESIVES. |
| | |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFY FOR THE |
| | NEW ROOF FRAMING. PROVIDE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | DESIGNER OF RECORD TO LIST FLORIDA PRODUCT APPROVAL |
| | NEXT TO EACH SPECIFIED CONNECTOR. |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | CITY AMENDMENTS. |
| | |
| | 3- PERMIT APPLICATION SPECIFIES ROOFING WORK. DESIGNER |
| | OF RECORD TO CLARIFY SCOPE OF ROOFING REQUIRED FOR THIS |
| | JOB. CLARIFY IF RE-ROOFING ENTIRE ROOF AREA OR JUST THE |
| | AREA OF WORK FOR NEW SKYLIGHT. DESIGNER OF RECORD TO |
| | SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC. |
| | 107.2.1.2 CITY AMENDMENTS. IF SPECIFYING SCREWS, THEN |
| | SPECIFY SIZE AND NUMBER OF SCREWS. IF SPECIFYING ROOF |
| | ADHESIVE, THEN SEE ROOF TILE PRODUCT APPROVAL FOR |
| | LISTED ADHESIVES. |
| | |
| | 4- SHEET D1.0: DESIGNER OF RECORD TO REVISE THE FLORIDA |
| | BUILDING CODE SPECIFIED ON THE CLASSIFICATION OF WORK. |
| | THE CURRENT CODE IS THE 2014 FBC NOT 2010 FBC. SEC. |
| | 553. FLORIDA STATUTE. |
| | |
| | 5- SHEET A1.0: REVISE THE BUILDING EXPOSURE AND |
| | CORRESPONDING DESIGN PRESSURES. THIS BUILDING IS |
| | LOCATED IN CLOSE PROXIMITY TO THE MANGONIA LAKE. IT |
| | LOOKS MORE LIKE EXPOSURE "D" RATHER THAN EXPOSURE "C". |
| | REVISE THE BUILDING EXPOSURE AND THE DESIGN PRESSURES |
| | ACCORDINGLY TO CORRESPOND TO EXPOSURE "D" OR PROVIDE |
| | COMPLETE RATIONAL ANALYSIS FOR AN INTERMEDIATE EXPOSURE |
| | AS REQUIRED BY THE EXCEPTION ON SEC. R301.2.1.4 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | NOTE: REVISE THE DESIGN PRESSURES FOR THE SKYLIGHT AND |
| | SLIDING GLASS DOORS SHOWN ON PLANS. KEEP IN MIND THAT |
| | THE PROPOSED SKYLIGHT IS LOCATED IN ROOF ZONE #2. |
| | |
| | 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT (THIS APPLIES EVEN FOR |
| | OWNER/BUILDERS) AND ALL DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE VALUE |
| | FOR ALL THE SCOPE OF WORK SHOWN ON PLANS AND INCLUDE |
| | THE DESIGN PROFESSIONAL FEES. |
| | |