| 2016-12-28 13:56:20 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| | SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE |
| | SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, SOLAR |
| | PANELS, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, ETC. A |
| | NOTE WILL SUFFICE. |
| | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, |
| | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP |
| | AND COMPLETIONS DOCUMENTS. |
| | 3. PROVIDE A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT |
| | AND APPARATUSES ABOVE THE FLOOD PLAIN LEVEL. |
| | 4. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING |
| | REQUIREMENTS. |
| | 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 6. SOLAR SYSTEM SHOWN ON THESE DOCUMENTS WILL BE |
| | SUBJECT TO A COMPLETE REVIEW UPON SEPARATE PERMIT |
| | APPLICATION. NOTE THAT ALL NEC 690 REQUIREMENTS MUST BE |
| | MET, EXAMPLE: GROUNDING SCHEME, BACK FED BREAKER SHOWN |
| | ON LOAD CENTER P2, SIGNAGE ETC.? |
| | 7. SHEET E2: LABEL ALL W/P RECEPTACLES TO BE GFCI |
| | PROTECTED PER NEC 210.8B |
| | 8. PROVIDE A GENERAL NOTE TO INDICATE NEC 300.5 BURIAL |
| | DEPTH REQUIREMENTS FOR ALL U/G CONDUITS. |
| | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY |
| | |
| | |