| Plan Review Notes For Permit 16120328 |
| Permit Number |
16120328 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-30 10:23:11 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO'S: | | | | | | 1] FEEDER CONDUCTOR FROM PANEL "A" TO PANEL "B" SHOULD | | | BE 3 GAUGE FOR 100 AMPS. FBC-R TABLE E3705.1 ALLOWABLE | | | AMPACITIES | | | | | | 2] BOND GAS IN ACCORDANCE WITH FBC-R SECTION E3609.7. |
|