| Plan Review Notes For Permit 16120328 |
| Permit Number |
16120328 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-02-08 17:18:48 | APPROVED WITH EXCEPTIONS - PROVISO | | | - SUBMIT TWO SETS OF ENHANCED FASTENING CALCULATIONS | | | FOR CERTAINTEED MODIFIED ROOFING SYSTEM W-68 FROM | | | FL2533-R16 FOR EXPOSURE D. FBC-R905.11.3 | | | - SUBMIT TWO SETS OF SIGNED AND SEALED SITE SPECIFIC | | | ENGINEERING FOR WINDLOADS WITH INSTALLATION DETAILS FOR | | | THE RELOCATED CARRIAGE DOORS AT THE CABANA. FBC-R612.2 | | | - SHOW THAT THE WINDOW OF THE RELOCATED CARRIAGE DOORS | | | IS IN COMPLIANCE WITH FBC-R308.4 HAZARDOUS LOCATIONS. | | | - SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN | | | APPROVED BY THE DESIGNER OF RECORD FOR THE SINGLE HUNG | | | WINDOW (E) IN THE SCHEDULE ON A400. FBC107.2.1 | | | - SUBMIT TWO SETS OF AN INSTALLATION SCHEDULE FOR EACH | | | OF THE OPENINGS THAT WILL HAVE ARMOR SCREEN FABRIC | | | HURRICANE. SPECIFY THE INSTALLATION TYPE, ANCHOR TYPE, | | | ANCHOR SPACING, ETC. FBC-R301.2.1.2 | | | |
|