| Plan Review Notes For Permit 16120328 |
| Permit Number |
16120328 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-10 19:00:55 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT HEATING AND COOLING EQUIPMENT SIZING | | | CALCULATIONS. FBCR-M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT AND APPLIANCES SHALL BE SIZED IN ACCORDANCE | | | WITH ACCA MANUAL S BASED ON BUILDING LOADS CALCULATED | | | IN ACCORDANCE WITH ACCA MANUAL J OR OTHER APPROVED | | | HEATING AND COOLING CALCULATION METHODOLOGIES. | | | | | | |
|