| 2016-12-22 11:08:17 | JOB PERMIT NUMBER: 16120328 |
| | JOB ADDRESS: 259 BARCELONA RD |
| | WEST PALM BEACH FLORIDA |
| | DATE: DECEMBER 22, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE RESIDENTIAL) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] POOL, LOW VOLTAGE, & GENERATOR SHALL BE SUBMITTED |
| | UNDER A SEPARATE PERMIT WITH SEPARATE SHOP DRAWINGS. |
| | ADD A NOTE. |
| | |
| | 2] ALL PERMANENT INSTALLED LUMINAIRES SHALL BE 75 % |
| | HIGH EFFICIENT. FBC-E SECTION R404.1 (A NOTE WILL |
| | SUFFICE). |
| | |
| | 3] RECESSED LIGHTING INSTALLED SHALL BE SEALED TO LIMIT |
| | AIR LEAKAGE BETWEEN CONDITIONED AND UNCONDITIONED |
| | SPACES. IF THE CANS ARE INSTALLED IN THERMAL INSULATION |
| | THE HOUSING SHALL BE LISTED IC-RATED. FBC-E SECTION |
| | R402.4.4 (A NOTE WILL SUFFICE). |
| | |
| | 4] CLARIFY IF MASTER BEDROOM GFCI RECEPTACLE OUTLETS |
| | ARE WITHIN 3' OF THE SINK PER FBC-R SECTION E3901.6 |
| | |
| | 5] IDENTIFY STAIRWAY SWITCH AS A 3-WAY PER FBC-R |
| | SECTION E3903.3 |
| | |
| | 6] PANEL "A" LOCATED IN THE UTILITY ROOM SHALL HAVE A |
| | MINIMUM 6'.5" HEIGHT WORKING SPACE FROM THE FINISHED |
| | FLOOR & THE DEDICATED SPACE SHALL HAVE NO FOREIGN |
| | SYSTEM (PLUMBING PIPES / MECHANICAL DUCTS) LOCATED IN |
| | THIS ZONE. FBC-R SECTION E3405. |
| | |
| | 7] CLARIFY IF PANEL "B" IS LOCATED IN A CLOTHES CLOSET |
| | THEREFORE IN VIOLATION OF FBC-R SECTION E3405.4. PLEASE |
| | IDENTIFY THIS AREA TO BE CLEAR OF THE PURPOSE IT |
| | SERVES. FBC 107 |
| | |
| | 8] ELIMINATE BONDING FROM MAIN GROUND ROD TO CABANA |
| | GROUND ROD, WHICH IS A VIOLATION OF NEC 250 (CREATING |
| | PARALLEL PATH). THE EGC SHALL BE BONDED AT PANEL "C" TO |
| | THE EQUIPMENT AND CONNECTED TO THE GROUND ROD |
| | (INTERCONNECTION NOT REQUIRED). REFERENCE NEC 250.32 |
| | |
| | 9] ADD AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| | IN ACCORDANCE WITH NEC 250.94. |
| | |
| | 10] PROVIDE PROPER SIGNAGE FOR OPTIONAL STAND BY |
| | SYSTEMS AT THE SERVICE EQUIPMENT PER NEC 702.7 |
| | |
| | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |