| Plan Review Notes For Permit 16120270 |
| Permit Number |
16120270 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-04 12:17:49 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16120270 | | | 12/28/16 | | | | | | 1) PROVIDE THE DIMENSIONS OF THE RETURN AIR GRILLS AT | | | THE MECHANICAL ROOM- 601.5 | | | | | | 2) SHOW THE LOCATION(S) OF THE REQUIRED SMOKE | | | DETECTOR(S) IN THE MECHANICAL ROOM- SECTION 606.2.2 | | | | | | 3) SHOW THE LOCATION OF THE O/A DUCT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|