| Plan Review Notes For Permit 16120270 |
| Permit Number |
16120270 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-01-12 17:08:30 | PROVISO 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] APPLY ARC-FLASH HAZARD WARNING LABEL TO ELECTRICAL | | | EQUIPMENT LIKELY TO BE WORKED ON WHILE ENERGIZED PER | | | NEC 110.16. | | | | | | 2] PULL BOX SHALL BE SIZED IN ACCORDANCE WITH NEC | | | 314.28. | | | |
|