| Plan Review Notes For Permit 16120265 |
| Permit Number |
16120265 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-08 10:18:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE REQUIRED DESIGN PRESSURES FOR THIS JOB, 20MRH, | | | EXPOSURE C: | | | ZONE 2: -67.8 | | | ZONE 3: -102.0 | | | | | | THE ASSEMBLY SELECTED, W-51, HAS A DP LIMITATION OF | | | -82.5. THE ASSEMBLY SELECTED DOES NOT MEET THE REQUIRED | | | DESIGN PRESSURE FOR ZONE 3, FBC R 301. | | | | | | 2. THE PRODUCT APPROVAL IS INCOMPLETE. THE EVALUATION | | | REPORT IS MISSING (PAGES APPLICABLE TO ALL ASSEMBLIES, | | | PAGES 1 THROUGH 6); FBC 107, PROVIDE. | | | | | | 3. SEE PAGE 6 (NOT INCLUDED IN SUBMITTAL) OF THE | | | PRODUCT APPROVAL, LIMITATION 5.7, A QUALIFIED DESIGN | | | PROFESSIONAL IS REQUIRED TO DETERMINE ATTACHMENT | | | DENSITY FOR ZONE 3. | | | | | | | | | |
|