2016-12-08 14:33:1816120249
 2 HARVARD CIRCLE , SUITE 300
 INTERIOR RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE PANEL SCHEDULES SHOWING THE NEW AND EXISTING
 CIRCUITS. INDICATE THE LOCATION OF THE MAIN
 DISCONNECTS. NEC 240.24, 408.4, 408.17
  
 PROVIDE A DESIGNATED LOCATION FOR THE PANEL BOARDS
 WHICH REMAIN CLEAR OF OBSTRUCTION AND STORAGE AT ALL
 TIMES. OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE
 VICINITY OF EASILY IGNITABLE MATERIAL. NEC 110.26,
 240.24
  
 PROVIDE CIRCUITRY DETAIL ON THE PLAN FOR THE
 EMERGENCY/EXIT LIGHTING. NEC 700.12(F)(4)
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405
  
  