| Plan Review Notes For Permit 16120249 |
| Permit Number |
16120249 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-08 14:33:18 | 16120249 | | | 2 HARVARD CIRCLE , SUITE 300 | | | INTERIOR RENOVATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE PANEL SCHEDULES SHOWING THE NEW AND EXISTING | | | CIRCUITS. INDICATE THE LOCATION OF THE MAIN | | | DISCONNECTS. NEC 240.24, 408.4, 408.17 | | | | | | PROVIDE A DESIGNATED LOCATION FOR THE PANEL BOARDS | | | WHICH REMAIN CLEAR OF OBSTRUCTION AND STORAGE AT ALL | | | TIMES. OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE | | | VICINITY OF EASILY IGNITABLE MATERIAL. NEC 110.26, | | | 240.24 | | | | | | PROVIDE CIRCUITRY DETAIL ON THE PLAN FOR THE | | | EMERGENCY/EXIT LIGHTING. NEC 700.12(F)(4) | | | | | | PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY | | | CONSERVATION REQUIREMENTS. FBC C405 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-373-3701 | | | [email protected] | | | |
|