2016-12-30 15:41:431ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. HOT WATER REQUIRED AT MOP SINK. PER FBC PL 607.1
  
 2. PLEASE PROVIDE SANITARY AND WATER RISER DIAGRAMS.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 3. PROVIDE MANUFACTURE SPECIFICATION FOR WATER HEATER
 AND WATER COOLER MUST SHOW APPROVED FOR OUTDOOR USE.
 PER WPB AMEND TO FBC 107.2.1
  
 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. PER FBC ACC 609.4
  
 5. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION, NOT 18"
 MIN. PER FBC ACC 604.2