Plan Review Notes
Plan Review Notes For Permit 16120222
Permit Number 16120222
Review Stop M
Sequence Number 1
Notes
Date Text
2016-12-22 16:16:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120222
 12/22/16
  
 1) REFER TO SECTION 404: PROVIDE AN EXHAUST VENTILATION
 CALCULATION FOR THE FAN IN THE GOLF CART GARAGE, AND
 INDICATE A SEQUENCE OF OPERATION.
  