| 2016-12-14 10:46:31 | JOB PERMIT NUMBER: 16120196 |
| | JOB ADDRESS: 1911 N FLAGLER DRIVE |
| | WEST PALM BEACH FLORIDA 33407 |
| | DATE: DECEMBER 14, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] SHOW EXITS SIGNS ON THE ELECTRICAL LIGHTING PLAN. |
| | FBC-1011. |
| | |
| | 2] PROVIDE AN OCCUPANCY SENSOR IN OFFICE SUITE 102. |
| | FBC-E SECTION C405.2.2.2. |
| | |
| | 3] PROVIDE A MOUNTING DETAIL FOR THE CEILING GRID LIGHT |
| | FIXTURES IN ACCORDANCE WITH NEC 410.36(B). SHOW |
| | SUPPORTING DETAIL IN COMPLIANCE WITH ACOUSTICAL SYSTEM |
| | PROVISIONS ASTM 635C & 636C. |
| | |
| | 4] PROVIDE PULL BOX SIZE TO MEET MINIMUM REQUIREMENTS |
| | OF NEC 314.28. |
| | |
| | 5] ADD A NOTE FOR SOURCE OF SUPPLY MARKING ON PANEL "B" |
| | PER NEC 408.4(B). |
| | |
| | 6] ADD A NOTE THAT LOW VOLTAGE SHALL BE UNDER A |
| | SEPARATE PERMIT. |
| | |
| | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |