| Plan Review Notes For Permit 16120133 |
| Permit Number |
16120133 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-03 09:41:04 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16120133 | | | 1/3/17 | | | | | | 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. PLEASE | | | PROVIDE AN AC LOAD CALCULATION THAT INCLUDES THE | | | ADDITIONAL HEAT GAIN FROM THE MAKEUP AIR, AND THAT | | | INDICATES THE ADDITIONAL LOAD DOES NOT EXCEED THE | | | CAPACITY OF THE EXISTING OR PROPOSED AC SYSTEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|