| Plan Review Notes For Permit 16120125 |
| Permit Number |
16120125 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-07 14:17:42 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 2. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 3. PROVIDE FLOOR PLAN SHOWING ALL GAS APPLIANCES AND | | | PIPING. WPB AMEND TO FBC 107.2.1 | | | | | | 4. PLANS CANNOT BE DRAWN IN PENCIL CLOUD AND NOTE FOR | | | PROPOSED GENERATOR IS IN PENCIL. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. |
|