| Plan Review Notes For Permit 16120116 |
| Permit Number |
16120116 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-12 06:57:56 | 1) SHOW THE DISTANCE FROM THE RELIEF VALVE ON THE LP | | | TANK TO THE EXTERIOR WALL OF THE STRUCTURE. COMPLY WITH | | | NFPA 58 SEC.6.3.4.2. | | | 2) SHOW THE DISTANCE OF THE LP TANK FROM THE PROPERTY | | | LINE.COMPLY WITH NFPA 58 TABLE 6.3.1. | | | 3) YOU HAVE SUBMITTED TWO DIFFERENT SIZING TABLES WITH | | | THIS PERMIT - ONE FOR A 10 PSI SYSTEM WITH DRISCOPLEX | | | PIPE AND ONE FOR A 11.0 INCH W.C.( LOW PRESSURE) SYSTEM | | | WITH SCH. 40 METALLIC PIPE BUT NO METALLIC PIPE IS | | | SHOWN.CLARIFY. SHOW WHAT THE PSI OF THE SYSTEM IS ON | | | THE PE PIPE. | | | 4) SHOW THE LOCATION OF THE U/G GAS LINE FROM THE TANK | | | TO ITS TERMINATION POINT ABOVE GROUND ON THE SURVEY. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|