| Plan Review Notes For Permit 16120108 |
| Permit Number |
16120108 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-12 18:51:05 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO'S | | | | | | 1] GFCI PROTECTION REQUIRED FOR BOAT HOIST. NEC | | | 210.8(C) | | | 2] 24" MINIMUM DEPTH REQUIRED WHEN PASSING UNDER | | | STREETS. NEC 300.5 (TABLE) |
|