Plan Review Notes
Plan Review Notes For Permit 16120098
Permit Number 16120098
Review Stop B
Sequence Number 1
Notes
Date Text
2017-01-04 19:00:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED WITHIN 600 FEET OF THE INLAND
 WATERWAY. THEREFORE, IT IS EXPOSURE CATEGORY D RATHER
 THAN C. FBC-R301.2.1.4.3 NOTE: THE EXTERIOR DOOR AND
 WINDOW PRESSURES WILL NEED TO BE REVISED FOR EXPOSURE
 D.
  
 2) SPECIFY ON THE PLANS THAT THIS IS A LEVEL 2
 ALTERATION PER FBC EXISTING BUILDING SECTION 504.
  
 3) THE PLANS REFERENCE THE 2010 EDITION OF THE FLORIDA
 PLUMBING CODE ON SHEET A.01. THE 2014 IS THE EDITION
 THAT WOULD APPLY.
  
 4) SPECIFY THE SIZE OF THE POWDER ROOM DOOR ON THE
 PLANS. FBC 107.2.1
  
 5) ON SHEET S.01 UNDER STRUCTURAL DESIGN CRITERIA, THE
 PARAPET HEIGHT ABOVE GRADE IS SPECIFIED AS 50 FEET. THE
 ELEVATIONS ON THE PLANS SHOW A TWO STOREY BUILDING WITH
 A SLOPED ROOF. THE MEAN ROOF HEIGHT (THE DISTANCE FROM
 GRADE TO THE AVERAGE OF THE ROOF EAVE HEIGHT AND THE
 HEIGHT TO THE HIGHEST POINT ON THE ROOF SURFACE) WHICH
 IS USED TO DETERMINE THE COMPONENT AND CLADDING
 PRESSURES LOOKS TO BE AROUND 21 FEET. FBC-R301.2.1
  
 6) THE EXTERIOR DOOR AND WINDOW PRESSURES ARE
 INCORRECT. THE POSITIVE PRESSURES WILL ALWAYS BE LESS
 THAN THE NEGATIVE PRESSURES. THIS BUILDING LOCATED IN
 EXPOSURE D WITH A 25 FT. MRH WILL HAVE WORST CASE
 PRESSURES OF +50.4, -67.5 PSF FOR A 10SQFT AREA IN WALL
 ZONE 5 (CORNERS). FBC-R301.2.1
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DBPR RULE
 61G20-3.001 THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR THE METAL ROOFING MATERIALS AND NEW EXTERIOR DOOR.
  
 8) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS WERE NOT REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4
  
 9) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  