| 2017-01-13 09:25:03 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SPECIFY FLOORING TO BE INSTALLED. | | | 2. PROVIDE ASTM E-90, ASTM E-492 AND IF WOOD FLOORING | | | ASTM E-84 (FLAMESPREAD) FOR FLOORING UNDERLAYMENT. | | | | | | FBC 603.1 FLAME SPREAD ? ASTM E-84 | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 49 | | | | | | | | | |
|