Plan Review Notes
Plan Review Notes For Permit 16120096
Permit Number 16120096
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-14 16:28:301ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] THE SCOPE OF WORK, JOB ADDRESS & APPLICABLE CODE
 SHALL APPEAR ON THE DRAWING ALONG WITH THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 CITY AMENDMENTS TO FBC 107.2.1.
  
 2] A MINIMUM 20 AMP CIRCUIT IS REQUIRED FOR THE
 BATHROOM. NEC 210.11(C)(3)
  
 3] SHOW A GFCI PROTECTED RECEPTACLE OUTLET WITHIN 3' OF
 BATH SINK EDGE. NEC 210.52 (D) & 210.8(A)(1).