| 2017-03-27 15:12:41 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16120091 | | | 3/27/17 | | | | | | 1) AS PREVIOUSLY NOTED THE PLAN INDEX DOES NOT MATCH | | | THE PLANS- SHEETS 3.1M AND 3.2M ARE EITHER MISSING OR | | | NOT APPLICABLE TO THE PROJECT. SHEETS 3.1P & 3.2P ARE | | | NOT IN THE INDEX. | | | | | | 2) THE SUBMITTED ENERGY COMPLIANCE FORM C402-2014 WHICH | | | IS FOR ALTERATIONS AND RENOVATIONS CANNOT BE USED FOR | | | THE PROPOSED PROJECT WHICH IS A CHANGE OF OCCUPANCY- | | | SEE NOTES AT THE TOP OF THE FORM AND SECTION C101.5.1.1 | | | FBC-14 ENERGY CONSERVATION. | | | | | | 3) THE AC CALCULATIONS ARE INCORRECTLY LISTING MIAMI AS | | | THE LOCATION OF THE PROJECT. | | | | | | 4) THE PLAN DOES NOT APPEAR TO SHOW HOW BALANCED AIR | | | FOR SYSTEMS 1A & 1B WILL BE ACCOMPLISHED. THE SYSTEMS | | | ARE SUPPLYING 4600 CFMS INTO THE TASTING ROOMS BUT ONLY | | | RECEIVING 2700 CFMS IN RETURN THROUGH THE 3- 24X24 " | | | GRILLS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|