Plan Review Notes
Plan Review Notes For Permit 16120091
Permit Number 16120091
Review Stop M
Sequence Number 4
Notes
Date Text
2017-03-27 15:12:414TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16120091
 3/27/17
  
 1) AS PREVIOUSLY NOTED THE PLAN INDEX DOES NOT MATCH
 THE PLANS- SHEETS 3.1M AND 3.2M ARE EITHER MISSING OR
 NOT APPLICABLE TO THE PROJECT. SHEETS 3.1P & 3.2P ARE
 NOT IN THE INDEX.
  
 2) THE SUBMITTED ENERGY COMPLIANCE FORM C402-2014 WHICH
 IS FOR ALTERATIONS AND RENOVATIONS CANNOT BE USED FOR
 THE PROPOSED PROJECT WHICH IS A CHANGE OF OCCUPANCY-
 SEE NOTES AT THE TOP OF THE FORM AND SECTION C101.5.1.1
 FBC-14 ENERGY CONSERVATION.
  
 3) THE AC CALCULATIONS ARE INCORRECTLY LISTING MIAMI AS
 THE LOCATION OF THE PROJECT.
  
 4) THE PLAN DOES NOT APPEAR TO SHOW HOW BALANCED AIR
 FOR SYSTEMS 1A & 1B WILL BE ACCOMPLISHED. THE SYSTEMS
 ARE SUPPLYING 4600 CFMS INTO THE TASTING ROOMS BUT ONLY
 RECEIVING 2700 CFMS IN RETURN THROUGH THE 3- 24X24 "
 GRILLS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  