2017-02-21 14:32:033RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16120091
 2/21/17
  
 1) PLEASE PROVIDE AN ACCURATE DRAWING INDEX ON SHEET
 C-1 THAT MATCHES THE RESUBMITTED PLANS.
  
 2) 3RD REQUEST FOR AC COOLING AND HEATING CALCULATIONS
 FOR THE NEW RTU.
  
 3) THE COMPLIANCE DATA FOR THE AC SYSTEMS AS SHOWN IN
 THE SUBMITTED ENERGYGAUGE COMPLIANCE FORM DOES NOT
 MATCH THE DATA SHOWN IN THE SCHEDULES FOR COOLING AND
 HEATING CAPACITIES, EFFICIENCY RATINGS, AND CFM SUPPLY.
 PLEASE NOTE THAT HEAT IS REQUIRED FOR THE TASTING ROOM,
 HOWEVER THE AHU SCHEDULE DOES NOT SHOW ANY PROVIDED-
 SEE SECTION 309.1.
  
 4) THE COMPLIANCE DATA FOR THE GLYCOL CHILLER SHOWN IN
 THE ENERGYGAUGE FORM DOES NOT MATCH THE DATA IN THE
 EQUIPMENT SCHEDULE. PLEASE NOTE THAT THE GLYCOL CHILLER
 IS A PROCESS CHILLER AND DOES NOT PROVIDE COOLING,
 HEATING, OR VENTILATION TO THE BUILDING. SEE SECTION
 1101.2 AND VERIFY THE CHILLER HAS BEEN TESTED IN
 ACCORDANCE WITH UL 207, 412, 471, OR 1995. SUBMIT
 MANUFACTURER'S SPECIFICATIONS TO VERIFY COMPLIANCE.
  
 5) 3RD REQUEST FOR THE BOILER EQUIPMENT SCHEDULE.
  
 6) SHEETS 3.3M & 3.4M: THE LOCATIONS OF THE COMBUSTION
 AIR DUCTS DO NOT MATCH.
  
 7) IF ELIMINATING EF-2 AS STATED IN THE RESPONSE
 NARRATIVE, THEN PLEASE REMOVE IT FROM THE PLANS AND THE
 EQUIPMENT SCHEDULE.
  
 8) 3RD REQUEST FOR MANUFACTURER'S SPECIFICATIONS OR
 CUT-SHEETS FOR THE BREWERY TANKS, KETTLES, AND OTHER
 ASSOCIATED EQUIPMENT.
  
 9) THE WORKING CLEARANCES FOR THE BREWERY EQUIPMENT AS
 SHOWN ON SHEET 1.1A DO NOT APPEAR AQDEQUATE FOR
 MAINTAINING AND SERVICING THE EQUIPMENT. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS AS PREVIOUSLY REQUESTED- SEE ALSO SECTION
 306.1.
  
 10) COMPLY WITH BUILDING COMMENTS FOR INSTALLATION OF
 ALL ROOFTOP MECHANICAL EQUIPMENT.
  
 11) SHEET 3.3M: VERIFY THE LOCATION OF THE KETTLE IS A
 MINIMUM 10' FROM THE AIR INTAKE TO RTU-1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  