| 2017-02-16 17:15:08 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16120091 |
| | ADD: 332 EVERNIA ST. |
| | CONT: MONTEIRO DEVELOPMENT INC. |
| | TEL: 561-346-6916 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. FEB. 16/2017 |
| | ACTION: DENIED |
| | |
| | ***PLEASE HAVE A MEETING WITH THE FAILED PLAN REVIEWERS |
| | BEFORE THE NEXT SUBMITTAL!!!*** |
| | |
| | 1-4) COMPLIED. |
| | |
| | 5) 2ND REQUEST. 2014 EXISTING BUILDING CODE SECTION |
| | 1013 ENERGY CONSERVATION SHALL COMPLY WITH THE FLORIDA |
| | BUILDING CODE, ENERGY CODE. MECHANICAL REVIEWERS 2ND |
| | REQUEST FOR FLORIDA ENERGY CONSERVATION CODE COMPLIANCE |
| | AND AC COOLING AND HEATING CALCULATIONS. |
| | |
| | 6) 3RD REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2014 |
| | EXISTING BUILDING CODE 1012.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 1012.2.1 AND 1012.2.2. |
| | 6A) 1012.2.1 FIRE SPRINKLER SYSTEM. |
| | |
| | |
| | 7)SEMI-COMPLIED. PLEASE SHOW HOW COMPLIANCE WITH |
| | SECTION 1012.1.4 ACCESSIBILITY OF THE 2014 EXISTING |
| | BUILDING CODE IS ACHIEVED. ALL BUILDINGS UNDERGOING A |
| | CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| | SECTION 1012.8 EXIST. BUILD. CODE. PLEASE SHOW ON THE |
| | LIFE SAFETY PLAN A1.4A. |
| | |
| | 7A)2ND REQUEST. DINING SURFACES. 226.1. WHERE DINING |
| | SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR |
| | DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND |
| | STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| | WITH 902. 178 X 0.05= 8.9 OR 9 OCCUPANTS PLANS ONLY |
| | SHOW 7 WHEEL CHAIR SPACES. |
| | |
| | 7B) SEMI-COMPLIED. WHEELCHAIR PLACEMENT FOR DISPERSION |
| | / BAR. . THE 2 ACCESSIBLE SPACES LOCATED IN FRONT OF |
| | THE BAR DOES NOT PROVIDE A CUT SECTION THROUGH THE BAR |
| | INDICATING THE HEIGHT OF THE BAR.. ACCESS. CODE 902.3 |
| | HEIGHT. THE TOPS OF DINING SURFACES SHALL BE 28 INCHES |
| | MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 7C) 2ND REQUEST. WHEELCHAIR PLACEMENT IS SHOWN ON THE |
| | PLANS BUT NOT THE CLEAR FLOOR SPACE. 902.2 CLEAR FLOOR |
| | OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305 |
| | POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED. |
| | KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | 7D)3RD REQUEST. 902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 8-12) COMPLIED. |
| | |
| | 13) 2ND REQUEST. ROOF TOP CURBS. SHEET 3.4M DOES SHOW A |
| | DETAIL FOR ANCHORING OF A ROOF TOP CURB TO THE ROOF TOP |
| | FRAMING. DETAILS SHOW 3X3 ANGLES BUT DOES NOT STATE IF |
| | TO BE WELDED TO THE TOP CHORD OF THE BAR JOIST, THERE |
| | IS NO INFORMATION AS TO THE TYPE OF WELDS, THE 3X3 |
| | ANGLES DOES NOT PROVIDE THE THICKNESS NOR THE LENGTH OF |
| | THE ANGLES. THE DESIGNER HAS NOT INDICATED POINT |
| | LOADING OF THE BAR JOIST AND OR STRENGTHENING OF BAR |
| | JOIST FOR THE ADDITIONAL LOADING. |
| | THE ROOF TOP CURB SIZE IS NOT PROVIDED, NOR PRODUCT |
| | APPROVALS FOR THE CURB OR MANUFACTURERS CUT SHEET. |
| | MISSING INFORMATION. ADMINISTRATIVE CODE 107.2.1.3. |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 14) 3RD REQUEST. SHEET 3.4M SHOWS A CONNECTION FOR THE |
| | ROOF TOP RTU TO THE CURB, THIS DETAIL DOES PROVIDE THE |
| | WIND SPEED THAT IT WAS DESIGNED FOR. THIS REVIEW THERE |
| | IS A NEW BRACKET, Z BRACKET BY MICRO METAL PLEASE |
| | PROVIDE THE MANUFACTURERS LITERATURE FOR THE END USE OF |
| | THIS BRACKET. |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | |
| | 15-20) COMPLIED. |
| | |
| | 21) COMPLIED. IMPACT FEES. |
| | |
| | 22) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |