2017-02-16 17:15:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120091
 ADD: 332 EVERNIA ST.
 CONT: MONTEIRO DEVELOPMENT INC.
 TEL: 561-346-6916
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. FEB. 16/2017
 ACTION: DENIED
  
 ***PLEASE HAVE A MEETING WITH THE FAILED PLAN REVIEWERS
 BEFORE THE NEXT SUBMITTAL!!!***
  
 1-4) COMPLIED.
  
 5) 2ND REQUEST. 2014 EXISTING BUILDING CODE SECTION
 1013 ENERGY CONSERVATION SHALL COMPLY WITH THE FLORIDA
 BUILDING CODE, ENERGY CODE. MECHANICAL REVIEWERS 2ND
 REQUEST FOR FLORIDA ENERGY CONSERVATION CODE COMPLIANCE
 AND AC COOLING AND HEATING CALCULATIONS.
  
 6) 3RD REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2014
 EXISTING BUILDING CODE 1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
 6A) 1012.2.1 FIRE SPRINKLER SYSTEM.
  
  
 7)SEMI-COMPLIED. PLEASE SHOW HOW COMPLIANCE WITH
 SECTION 1012.1.4 ACCESSIBILITY OF THE 2014 EXISTING
 BUILDING CODE IS ACHIEVED. ALL BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 SECTION 1012.8 EXIST. BUILD. CODE. PLEASE SHOW ON THE
 LIFE SAFETY PLAN A1.4A.
  
 7A)2ND REQUEST. DINING SURFACES. 226.1. WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 178 X 0.05= 8.9 OR 9 OCCUPANTS PLANS ONLY
 SHOW 7 WHEEL CHAIR SPACES.
  
 7B) SEMI-COMPLIED. WHEELCHAIR PLACEMENT FOR DISPERSION
 / BAR. . THE 2 ACCESSIBLE SPACES LOCATED IN FRONT OF
 THE BAR DOES NOT PROVIDE A CUT SECTION THROUGH THE BAR
 INDICATING THE HEIGHT OF THE BAR.. ACCESS. CODE 902.3
 HEIGHT. THE TOPS OF DINING SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 7C) 2ND REQUEST. WHEELCHAIR PLACEMENT IS SHOWN ON THE
 PLANS BUT NOT THE CLEAR FLOOR SPACE. 902.2 CLEAR FLOOR
 OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED.
 KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 7D)3RD REQUEST. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 8-12) COMPLIED.
  
 13) 2ND REQUEST. ROOF TOP CURBS. SHEET 3.4M DOES SHOW A
 DETAIL FOR ANCHORING OF A ROOF TOP CURB TO THE ROOF TOP
 FRAMING. DETAILS SHOW 3X3 ANGLES BUT DOES NOT STATE IF
 TO BE WELDED TO THE TOP CHORD OF THE BAR JOIST, THERE
 IS NO INFORMATION AS TO THE TYPE OF WELDS, THE 3X3
 ANGLES DOES NOT PROVIDE THE THICKNESS NOR THE LENGTH OF
 THE ANGLES. THE DESIGNER HAS NOT INDICATED POINT
 LOADING OF THE BAR JOIST AND OR STRENGTHENING OF BAR
 JOIST FOR THE ADDITIONAL LOADING.
 THE ROOF TOP CURB SIZE IS NOT PROVIDED, NOR PRODUCT
 APPROVALS FOR THE CURB OR MANUFACTURERS CUT SHEET.
 MISSING INFORMATION. ADMINISTRATIVE CODE 107.2.1.3.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 14) 3RD REQUEST. SHEET 3.4M SHOWS A CONNECTION FOR THE
 ROOF TOP RTU TO THE CURB, THIS DETAIL DOES PROVIDE THE
 WIND SPEED THAT IT WAS DESIGNED FOR. THIS REVIEW THERE
 IS A NEW BRACKET, Z BRACKET BY MICRO METAL PLEASE
 PROVIDE THE MANUFACTURERS LITERATURE FOR THE END USE OF
 THIS BRACKET.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 15-20) COMPLIED.
  
 21) COMPLIED. IMPACT FEES.
  
 22) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER