| 2017-02-06 11:39:51 | 2ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. 3.1P THE 1" GLYCOL DROPS TO THE TANKS ARE |
| | MARKED AS CHW, CHR THE MAINS AND LEGEND IS SHOWN AS |
| | CWS, CWR PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. 3.2P THE WATER CLOSETS IN-THE WOMENS BATHROOM |
| | ARE NOT SHOWN ON THE WATER RISER . PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 3. SHT 3,2P THE HWC IN MANS BATHROOM IS SHOWN AS A UR |
| | ON WATER RISER PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. PLEASE INCLUDE ON THE PLAN BACK FLOW REQUIRED ON |
| | WATER FILTER. PER FBC PL 608.3 |
| | |
| | 5. PLEASE PROVIDE A NOTE ON THE PLANS THAT TEMPERED |
| | WATER SHALL BE DELIVERED FROM LAVATORIES AND GROUP WASH |
| | FIXTURES LOCATED IN PUBLIC TOILET FACILITIES PROVIDED |
| | FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER |
| | SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |