Plan Review Notes
Plan Review Notes For Permit 16120091
Permit Number 16120091
Review Stop P
Sequence Number 2
Notes
Date Text
2017-02-06 11:39:512ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. 3.1P THE 1" GLYCOL DROPS TO THE TANKS ARE
 MARKED AS CHW, CHR THE MAINS AND LEGEND IS SHOWN AS
 CWS, CWR PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. 3.2P THE WATER CLOSETS IN-THE WOMENS BATHROOM
 ARE NOT SHOWN ON THE WATER RISER . PER WPB AMEND TO FBC
 107.2.1
  
 3. SHT 3,2P THE HWC IN MANS BATHROOM IS SHOWN AS A UR
 ON WATER RISER PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. PLEASE INCLUDE ON THE PLAN BACK FLOW REQUIRED ON
 WATER FILTER. PER FBC PL 608.3
  
 5. PLEASE PROVIDE A NOTE ON THE PLANS THAT TEMPERED
 WATER SHALL BE DELIVERED FROM LAVATORIES AND GROUP WASH
 FIXTURES LOCATED IN PUBLIC TOILET FACILITIES PROVIDED
 FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  