2017-01-26 11:01:012ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16120091
 1/26/17
  
 MANY OF THE 1ST REVIEW COMMENTS STILL EXIST OR HAVE NOT
 BEEN ADDRESSED ENTIRELY. PLEASE NOTE THAT A 4X PLAN
 REVIEW FEE MAY APPLY IF THE PLAN IS DISAPPROVED A THIRD
 TIME FOR THE SAME CODE VIOLATIONS- SECTION 553.80
 FLORIDA STATUTES.
  
 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS
 (1ST REVIEW COMMENT #2).
  
 2) 2ND REQUEST FOR DOCUMENTATION OF FLORIDA ENERGY
 CONSERVATION CODE COMPLIANCE (COMMENT #3).
  
 3) 2ND REQUEST FOR COMPLIANT O/A CALCULATIONS. PLEASE
 SEE SHEET1.4A AND ADJUST THE BREWERY AREA CALCULATION
 USING THE 14 PERSON OCCUPANT LOAD (COMMENT #4).
  
 3A) THE CORRECTED O/A CALCULATION FOR AHU-1 INDICATES
 THAT AN ERV IS REQUIRED FOR THE SYSTEM- SEE SECTION AND
 TABLE C403.2.6 FBC-14 ENERGY CONSERVATION.
  
 4) 2ND REQUEST TO HOW THE C02 SENSOR AND LABEL THE AHU
 ON SHEET 3.3M (COMMENTS # 5 & 11).
  
 5) 2ND REQUEST FOR THE BOILER EQUIPMENT SCHEDULE TO BE
 PLACED ON THE PLAN- PLEASE NOTE THE SUBMITTED CUT
 SHEETS SHOW MULTIPLE MODELS OF VARYING CAPACITIES
 (COMMENT #7).
  
 6) 2ND REQUEST FOR COMPLIANT COMBUSTION AIR DUCT
 DRAWINGS. PLEASE SEE SECTION 304.11(4) DBC-14 FUEL GAS:
 SEPARATE DUCTS ARE REQUIRED IF USING THE TWO-OPENING
 METHOD IN THE BOILER ROOM (COMMENT #9).
  
 7) 2ND REQUEST FOR A EXHAUST VENTILATION CALCULATION
 FOR EF-2 (COMMENT #13).
  
 8) 2ND REQUEST FOR AN EQUIPMENT SCHEDULE FOR THE NEW
 O/A MOTORIZED DAMPER- SEE C402.4.5.2 (COMMENT #14).
  
 9) 2ND REQUEST FOR MANUFACTURER'S SPECIFICATIONS OR
 "CUT SHEETS" FOR THE BREWERY TANKS AND KETTLES (COMMENT
 #16).
  
 10) 2ND REQUEST TO ENLAREGE THE PRINT UNDER THE TANKS
 ON SHEET 1.5A ( COMMENT #17).
  
 11) 2ND REQUEST TO [PROVIDE WORKING CLEARANCE
 DIMENSIONS AROUND THE TANKS AND KETTLES ( COMMENT #18).
  
 12) 2ND REQUEST TO PROVIDE CODE-COMPLIANT GUARDS AT THE
 ROOF EDGES WHERE REQUIRED. THE REVISED PLAN SHOWS 36"
 HIGH GUARDS HOWEVER 42" GUARDS ARE REQUIRED PER SECTION
 304.11- PLEASE CORRECT (COMMENT #22).
  
 13) 2ND REQUEST FOR THE WIND DESIGN CRITERIA FOR
 ROOFTOP MECHANICAL INSTALLATIONS. PLEASE PLACE THE
 CRITERIA ( COMMENT #23).
  
 14) 2ND REQUEST FOR THE ROOF STAND NOA (COMMENT #23).
 PLEASE NOTE THAT THE ROOF STAND DOCUMENT SUBMITTED IS
 NOT VALID UNLESS IT IS AN APPROVED MIAMI-DADE NOA OR
 FL. PRODUCT APPROVAL. NO COVER SHEET WAS SUBMITTED TO
 VALIDATE THE DOCUMENT, AND THE SHEETS ALL HAVE COPIED
 ENGINEER'S SIGNATURES AND SEALS. THE CORRECT SUBMITTAL
 MUST ALSO BE MARKED UP BY THE EOR AS PREVIOUSLY
 REQUESTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  