| Plan Review Notes For Permit 16120091 |
| Permit Number |
16120091 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-02-03 16:33:26 | GAS COMMENTS: | | | 1. IT APPEARS THAT THE RISER DIAGRAM HAS NOT BEEN | | | REVISED IT DOES NOT REFLECT WHAT IS STATED IN YOUR | | | RESPONSE LETTER THE PLAN VIEW DOES REFLECT YOUR | | | RESPONSE. PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1 | | | | | | PREVIOUS COMMENTS : | | | | | | 3. AT THE END OF THE BRANCH FOR THE BOILER IT SHOWS 17' | | | @ 11/2"(399K) WHAT IS THIS FOR. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 6. PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL INDOOR | | | GAS FIRED APPLIANCES. FBC-2014 FUEL GAS CODE SEC. 304 | | | | | | 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | | NFPA 58, NFPA 50-51, NSF/ANSI 18-51 AND FBC-2014 FUEL | | | GAS SEC. 402.2 | | | | | | 8. THE ROOF PLAN SHOWS A FLUE FOR THE KETTLE IS IT A | | | GAS FIRED APPLIANCE. PER FBC FG TABLE 402.4(2) | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|