Plan Review Notes
Plan Review Notes For Permit 16120091
Permit Number 16120091
Review Stop G
Sequence Number 2
Notes
Date Text
2017-02-03 16:33:26 GAS COMMENTS:
 1. IT APPEARS THAT THE RISER DIAGRAM HAS NOT BEEN
 REVISED IT DOES NOT REFLECT WHAT IS STATED IN YOUR
 RESPONSE LETTER THE PLAN VIEW DOES REFLECT YOUR
 RESPONSE. PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 PREVIOUS COMMENTS :
  
 3. AT THE END OF THE BRANCH FOR THE BOILER IT SHOWS 17'
 @ 11/2"(399K) WHAT IS THIS FOR. PER WPB AMEND TO FBC
 107.2.1
  
 6. PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL INDOOR
 GAS FIRED APPLIANCES. FBC-2014 FUEL GAS CODE SEC. 304
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, NFPA 50-51, NSF/ANSI 18-51 AND FBC-2014 FUEL
 GAS SEC. 402.2
  
 8. THE ROOF PLAN SHOWS A FLUE FOR THE KETTLE IS IT A
 GAS FIRED APPLIANCE. PER FBC FG TABLE 402.4(2)
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  