| Plan Review Notes For Permit 16120091 |
| Permit Number |
16120091 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-24 11:29:31 | THE FOLLOWING PROVISO NOTES WERE ADDED TO THE RISER | | | PLAN. | | | | | | NEC.110.16 | | | ARC-FLASH WARNING LABELING IS REQUIRED FOR THE SERVICE, | | | PANEL BOARDS AND MAIN DISCONNECTS | | | | | | NEC 408.3 | | | HIGH- LEG IDENITIFICATION IS REQUIRED AT THE ELECTRICAL | | | SERVICE AND PANELBOARDS |
|