Plan Review Notes
Plan Review Notes For Permit 16120091
Permit Number 16120091
Review Stop B
Sequence Number 2
Notes
Date Text
2017-01-27 15:18:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120091
 ADD: 332 EVERNIA ST.
 CONT: MONTEIRO DEVELOPMENT INC.
 TEL: 561-346-6916
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JAN. 27/2017
 ACTION: DENIED
  
 1)2ND REQUEST!!! THE COVERSHEET C-1 LIST THIS PROJECT
 AS A LEVEL III ALTERATION. PLEASE BE AWARE THE LAST
 KNOWN USE OF THIS SPACE WAS A GYM AN A3 OCCUPANCY. THIS
 IS A CHANGE OF USE WITHIN THE SAME OCCUPANCY GROUP TO
 AN A2 TAVERNS AND BARS. PLEASE UPDATE THE PLANS TO THE
 REQUIREMENTS OF SECTION 1001.3 CHANGE OF OCCUPANCY
 CLASSIFICATION, THE 2014 EXISTING BUILDING CODE.
 EXISTING BUILDING CODE 1001.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 1002
 THROUGH 1012 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 2-4) COMPLIED.
  
 5) 2ND REQUEST. 2014 EXISTING BUILDING CODE SECTION
 1013 ENERGY CONSERVATION SHALL COMPLY WITH THE FLORIDA
 BUILDING CODE, ENERGY CODE. MECHANICAL REVIEWERS 2ND
 REQUEST FOR FLORIDA ENEERGY CONSERVATION CODE
 COMPLIANCE AND AC COOLING AND HEATING CALCULATIONS.
  
 6) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2014
 EXISTING BUILDING CODE 1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
 6A) 1012.2.1 FIRE SPRINKLER SYSTEM.
  
  
 7)SEMI-COMPLIED. PLEASE SHOW HOW COMPLIANCE WITH
 SECTION 1012.1.4 ACCESSIBILITY OF THE 2014 EXISTING
 BUILDING CODE IS ACHIEVED. ALL BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 SECTION 1012.8 EXIST. BUILD. CODE. PLEASE SHOW ON THE
 LIFE SAFETY PLAN A1.4A.
  
 7A)2ND REQUEST. DINING SURFACES. 226.1. WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 178 X 0.05= 8.9 OR 9 OCCUPANTS.
  
 7B) SEMI ?COMPLIED. SHEET 1.3A & 1.4A BOTH SHOW
 WHEELCHAIR PLACEMENT FOR DISPERSION. THE 2 ACCESSIBLE
 SPACES LOCATED IN FRONT OF THE BAR DOES NOT PROVIDE A
 CUT SECTION THROUGH THE BAR INDICATING THE HEIGHT OF
 THE BAR. SHEET 1.7A THE BAR SECTION GIVEN DOES NOT EVEN
 PROVIDE THE BAR HEIGHT. ACCESS. CODE 902.3 HEIGHT. THE
 TOPS OF DINING SURFACES SHALL BE 28 INCHES MINIMUM AND
 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 7C) SEMI-COMPLIED. WHEELCHAIR PLACEMENT IS SHOWN ON THE
 PLANS BUT NOT THE CLEAR FLOOR SPACE. 902.2 CLEAR FLOOR
 OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED.
 KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 7D)2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 8-12) COMPLIED.
  
 13) 2ND REQUEST. ROOF TOP CURBS. SHEET 3.4M DOES SHOW A
 DETAIL FOR ANCHORING OF A ROOF TOP CURB TO THE ROOF TOP
 FRAMING. ALSO SUBMITTED IN THE 2ND REVIEW IS A NOA FOR
 THYBAR TC-5 STYLE STEEL ROOF ?CURB FOR CARRIER ROOF TOP
 UNITS AND ANCHORING TO THE ROOF TOP FRAMING. . WHICH IS
 TO BE USED IN THIS INSTALLATION?
 1ST ROUND COMMENT. SHEET 3.4M SHOWS ROOF TOP EQUIPMENT.
 RTU 1 IS NOT CLEAR IF THIS UNIT IS EXISTING OR NEW.
 DETAILS SHOW 3X3 ANGLES TO BE WELDED TO THE TOP CHORD
 OF THE BAR JOIST, THERE IS NO INFORMATION AS TO THE
 TYPE OF WELDS, THE 3X3 ANGLES DOES NOT PROVIDE THE
 THICKNESS NOR THE LENGTH OF THE ANGLES. THE DESIGNER
 HAS NOT INDICATED POINT LOADING OF THE BAR JOIST AND OR
 STRENGTHENING OF BAR JOIST FOR THE ADDITIONAL LOADING.
 THE ROOF TOP CURB SIZE IS NOT PROVIDED, NOR PRODUCT
 APPROVALS FOR THE CURB WERE SUBMITTED.
 MISSING INFORMATION. ADMINISTRATIVE CODE 107.2.1.3.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 14) 2ND REQUEST. SHEET 3.4M ALSO SHOWS A CONNECTION FOR
 THE ROOF TOP RTU TO THE CURB, THIS DETAIL DOES PROVIDE
 THE WIND SPEED THAT IT WAS DESIGNED FOR.
 IF THE THYBAR NOA IS GOING TO BE THE METHOD OF
 INSTALLATION THEN SHOW COMPLIANCE WITH:
 THYBAR TC-5 STEEL ROOF CURB FOR CARRIER ROOFTOP UNITS
 NOA15-0218.11, PLEASE NOTE TECH PAGE 5 OF 5. RESTRAINT
 BRACKET QUANTITY IS DETERMINED BY PROJECT SPECIFIC
 CALCULATIONS, PERFORMED BY A FLORIDA LICENSED PE OR
 FLORIDA REGISTERED ARCHITECT THAT CONSIDER THE UNIQUE
 COMBINATION OF THE UNIT SIZE AND APPLICABLE LATERAL AND
 UPLIFT PRESSURES FOR EACH JOB. PLEASE PROVIDE
 CALCULATION FOR HOW MANY BRACKETS WILL BE NEEDED FOR
 EACH TYPE OF UNIT.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 15-16) COMPLIED. ROOF TOP ACCESS/ ROOF TOP GUARDS.
  
 17) NOT REQUIRED. MECHANICAL SCREENS
  
 18) AGAIN THE PLANS INDICATE ON SHEET 3.4M A DETAIL FOR
 MOUNTING ROOF TOP STANDS AND WHAT APPEARS TO BE A
 PRODUCT APPROVAL NO COVERSHEET INDICATING IT IS A
 FLORIDA APPROVAL OR A NOA. IF THE TECHNICAL SHEETS
 SUBMITTED ARE AN APPROVALS, PLEASE CIRCLE THE CORRECT
 CHARTS, FOR WIND SPEED, ANCHOR TYPES CONFIGURATION,
 UNIT DIMENSIONS, STAND HEIGHT AND EXPOSURE TYPE.
  
 1ST ROUND OF COMMENTS.
 SHEET 3.4M ALSO SHOWS NEW ROOF TOP A/C STANDS. PRODUCT
 APPROVALS FOR ROOF TOP STANDS MUST SHOW ALL TABLES
 WITHIN THE PRODUCT APPROVAL TO BE IDENTIFIED THAT ARE
 PERTINENT TO THE INSTALLATION, THEN REVIEWED BY THE
 DESIGNER OF RECORD.
  
 19-20) COMPLIED.
  
 21) COMPLIED. IMPACT FEES.
  
 22) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT