| 2016-12-19 15:58:14 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THERE IS 2 DIFFERENT SHT. 3.0P ONE WITH SANITARY ONE |
| | WITH WATER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. 3.0P NOTE IN JANITORS CLOSET SHOWS 50 GAL |
| | ELECTRIC WATER HEATER THE OTHER 3.0P SHOWS A TANKLESS |
| | WATER HEATER PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 3. SHT. 3.0P ON THE PIPING LEGEND UNDER AIR PVC IS NOT |
| | APPROVED TO USE FOR COMPRESSED AIR PER MANUFACTURE |
| | SPECIFICATIONS PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. WHAT TYPE OF PIPING IS BEING USED ON THE CO2 PIPING |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. ON THE PIPING LEGEND IT SHOWS CWS AS CHILLED GLYCOL |
| | SUPPLY AND CWR AS CHILLED GLYCOL RETURN ON THE PIPING |
| | IT SHOWS CHW, CHR, CHS THESE ARE NOT SHOWN ON THE |
| | PIPING LEGEND PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 6. SHT. 3.2P THE NOTE ON THE WATER RISER SAYS THAT |
| | SYSTEM WATER PIPING BY BREWERY INSTALLER ANY CONTACTOR |
| | WORKING ON THE POTABLE WATER SYSTEM SHALL BE A LIC |
| | PLUMBING CONTACTOR. PER FS 489 |
| | |
| | 7. 3.2 P DRAIN FOR 3 COMP SINK AND HAND SINK NEXT TO |
| | KEG WASH ARE NOT SHOWN ON RISER DIAGRAM PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |