Plan Review Notes
Plan Review Notes For Permit 16120091
Permit Number 16120091
Review Stop G
Sequence Number 1
Notes
Date Text
2016-12-19 12:11:011ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SHT. 3.0P UNDER THE PLUMBING NOTES IT SHOWS A
 PARTIAL GAS RISER FOR THE TANKLESS WATER HEATER PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. ON THE GAS RISER THE BRANCH TO THE BOILER SHOWS 630K
 ON THE FIRST TO SECTION THEN IT CHANGES TO 399K PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. AT THE END OF THE BRANCH FOR THE BOILER IT SHOWS 17'
 @ 11/2"(399K) WHAT IS THIS FOR. PER WPB AMEND TO FBC
 107.2.1
  
 4. BRANCH TO TANLESS HEATER SHALL BE 1" SIZED PER THE
 LONGEST LENGTH METHOD. PER FBC FG TABLE 402.4(2)
  
 5. BRANCH TO BOILER SHALL BE 11/2" SIZED PER THE
 LONGEST LENGTH METHOD. PER FBC FG TABLE 402.4(2)
  
 6. PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL INDOOR
 GAS FIRED APPLIANCES. FBC-2014 FUEL GAS CODE SEC. 304
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 8. THE ROOF PLAN SHOWS A FLUE FOR THE KETTLE IS IT A
 GAS FIRED APPLIANCE. PER FBC FG TABLE 402.4(2)
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  