| 2016-12-19 12:11:01 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | GAS COMMENTS: |
| | |
| | 1. SHT. 3.0P UNDER THE PLUMBING NOTES IT SHOWS A |
| | PARTIAL GAS RISER FOR THE TANKLESS WATER HEATER PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. ON THE GAS RISER THE BRANCH TO THE BOILER SHOWS 630K |
| | ON THE FIRST TO SECTION THEN IT CHANGES TO 399K PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. AT THE END OF THE BRANCH FOR THE BOILER IT SHOWS 17' |
| | @ 11/2"(399K) WHAT IS THIS FOR. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. BRANCH TO TANLESS HEATER SHALL BE 1" SIZED PER THE |
| | LONGEST LENGTH METHOD. PER FBC FG TABLE 402.4(2) |
| | |
| | 5. BRANCH TO BOILER SHALL BE 11/2" SIZED PER THE |
| | LONGEST LENGTH METHOD. PER FBC FG TABLE 402.4(2) |
| | |
| | 6. PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL INDOOR |
| | GAS FIRED APPLIANCES. FBC-2014 FUEL GAS CODE SEC. 304 |
| | |
| | 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| | |
| | 8. THE ROOF PLAN SHOWS A FLUE FOR THE KETTLE IS IT A |
| | GAS FIRED APPLIANCE. PER FBC FG TABLE 402.4(2) |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |