Plan Review Notes
Plan Review Notes For Permit 16120091
Permit Number 16120091
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-12-12 16:46:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 1.0 A - WITHIN THE REAR EXIT CORRIDOR LEADING
 TO THE EXIT THERE IS THAT OPENS INTO THE EXIT CORRIDOR
 ENCROACHING ON THE REQUIRED EXIT WIDTH.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 1.2.1.4.3 DOOR LEAF ENCROACHMENT
 1.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 2) SHEET 1.4 A - A NOTE IS INDICATING EXITS PROVIDED =
 3, ONLY TWO(2) EXITS ARE INDICATED, A DOUBLE SWING
 FRONT DOOR AND A SINGLE SWING REAR DOOR.
  
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
  
 3) SHEET 1.4 A - A NOTE INDICATES EXIT CAPACITY OF .3
 IS BEING USED.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS, TABLE 7.3.3.1
 IDENTIFIES 0.2 FOR EGRESS CAPACITY CLACULATION FOR
 LEVEL COMPONETS AND RAMPS.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
  
 4) SHEET 1.0 A - THE FRONT EXIT AND REAR OUTSIDE EXIT
 AREAS APPEAR TO INDICATE RAMPS. THERE ARE NO DETAILS
 INDICATED FOR EACH OF THE RAMPS.
  
 PLEASE PROVIDE ALL APPLICABLE RAMP DETAILS PER
 COMPLAINCE WITH NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
  
  
 5) SHEET 1.0 A AND ALL OTHER APPLICABLE SHEETS - A
 BOILER AND BOLIER ROOM IS INDICATED. NO BOILER
 INFORMATION, SPEC/EQUIPMENT SHEETS ARE PROVIDED
  
 PLEASE PROVIDE A NOTE THAT THE BOILER INSTALLATION
 SHALL BE UNDER SEPARATE PERMIT.
  
 PLEASE PROVIDE A NOTE INDICATING THE BOILER
 INSTALLATION SHALL COMPPLY WITH THE REQUIRMENTS OF NFPA
 85, BOILER AND COMBUSTION SYSTEMS HAZARDS CODE.
  
  
  
 6) SHEET 1.4 A - A BOILER IS INDICATED WITHIN A 2 HOUR
 RATED FIRE WALL ENCLOSURE. THE EXTERIOR WALL IS NOT
 INDICATED AS HAVING ANY RATING. THE EXTERIOR WALL LIES
 DIRECTLY OPPOSITE A PARKING LOT AND AN AREA DEFINED AS
 LEADING TO A PUBLIC WAY FOR AN ADJACENT BUILDING EXIT.
 THE EXTEIOR WALL SHALL HAVE THE SAME RATING AS THE
 OTHER WALLS SURROUNDING THE BOILER.
  
 PER NFPA 101, CHAPTER 12
  
 12.3.2.1 SERVICE EQUIPMENT, HAZARDOUS OPERATIONS OR
 PROCESSES, AND STORAGE FACILITIES.
 12.3.2.1.1 ROOMS CONTAINING HIGH-PRESSURE BOILERS,
 REFRIGERATING MACHINERY OF OTHER THAN THE DOMESTIC
 REFRIGERATOR TYPE, LARGE TRANSFORMERS, OR OTHER SERVICE
 EQUIPMENT SUBJECT TO EXPLOSION SHALL MEET BOTH OF THE
 FOLLOWING REQUIREMENTS:
 (1) SUCH ROOMS SHALL NOT BE LOCATED DIRECTLY UNDER OR
 ABUTTING REQUIRED EXITS.
 (2) SUCH ROOMS SHALL BE SEPARATED FROM OTHER PARTS OF
 THE BUILDING BY FIRE BARRIERS IN ACCORDANCE WITH
 SECTION 8.3 HAVING A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING OR SHALL BE PROTECTED BY AUTOMATIC EXTINGUISHING
 SYSTEMS IN ACCORDANCE WITH SECTION 8.7.
  
 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD GREATER THAN THAT NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE
 PROVIDED BY ONE OF THE FOLLOWING MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11
 THROUGH 43.
  
 PLEASE PROVIDE THE RATING OF THE EXTERIOR WALL THAT
 PROTECTS THE EXTERIOR PUBLIC WAY.
  
  
  
  
 7) SHEET 1.0 A - DOOR # 5 IS INDICATED WITHIN A 2 HOUR
 WALL. DOORS CONTAINED WITH A FIRE RATED WALL SHALL HAVE
 AUTOMATIC DOOR CLOSERS. THE DOOR SCHEDULE DOES NOT
 INDICATE A DOOR CLOSER FOR DOOR # 5.
  
 8.7.1.3 DOORS IN BARRIERS REQUIRED TO HAVE A FIRE
 RESISTANCE RATING SHALL HAVE A MINIMUM ?-HOUR FIRE
 PROTECTION RATING AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING IN ACCORDANCE WITH 7.2.1.8.
  
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
 8) SHEET 1.0 A - THE BOLIER IS AN EXPOSION HAZARD.
  
 8.7.2* EXPLOSION PROTECTION. WHERE HAZARDOUS PROCESSES
 OR STORAGE IS OF SUCH A CHARACTER AS TO INTRODUCE AN
 EXPLOSION POTENTIAL, AN EXPLOSION VENTING SYSTEM OR AN
 EXPLOSION SUPPRESSION SYSTEM SPECIFICALLY DESIGNED FOR
 THE HAZARD INVOLVED SHALL BE PROVIDED.
  
  
 PLEASE PROVIDE OR EXPLAIN/CLARIFY.
  
  
 9) SHEET 1.0 A AND ALL OTHER APPLICABLE SHEETS - A
 FERMENTATION ROOM (INDUSTRIAL) IS INDICATED ALONG WITH
 STORAGE (STORAGE) IN THE SAME ROOM WITH NO SEPARATION
 FROM THE ASSEMBLY. IS THIS A MIXED OCCUPANCY, SEPARATED
 OCCUPANCY OR MULTIPLE OCCUPANCY CLASSIFICATION?
  
 PLEASE EXPLAIN OR CLARIFY. PROVIDE FOR THE APPLICABLE
 OCCUPANCY SEPARATION OF EACH AREA AND/OR PROVIDE FOR
 THE REQUIRERMENTS OF THE MOST RESTRICTIVE OCCUPANCY. A
 MIXED NONSEPARATED OCCUPANY WILL REQUIRE AN 1 HOUR
 SEPARATION OR FIRE SPRINKLER PROTECTION.
  
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  