| Date |
Text |
| 2016-12-12 16:46:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET 1.0 A - WITHIN THE REAR EXIT CORRIDOR LEADING |
| | TO THE EXIT THERE IS THAT OPENS INTO THE EXIT CORRIDOR |
| | ENCROACHING ON THE REQUIRED EXIT WIDTH. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 1.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 1.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| | OPEN. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 2) SHEET 1.4 A - A NOTE IS INDICATING EXITS PROVIDED = |
| | 3, ONLY TWO(2) EXITS ARE INDICATED, A DOUBLE SWING |
| | FRONT DOOR AND A SINGLE SWING REAR DOOR. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 3) SHEET 1.4 A - A NOTE INDICATES EXIT CAPACITY OF .3 |
| | IS BEING USED. |
| | |
| | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS, TABLE 7.3.3.1 |
| | IDENTIFIES 0.2 FOR EGRESS CAPACITY CLACULATION FOR |
| | LEVEL COMPONETS AND RAMPS. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 4) SHEET 1.0 A - THE FRONT EXIT AND REAR OUTSIDE EXIT |
| | AREAS APPEAR TO INDICATE RAMPS. THERE ARE NO DETAILS |
| | INDICATED FOR EACH OF THE RAMPS. |
| | |
| | PLEASE PROVIDE ALL APPLICABLE RAMP DETAILS PER |
| | COMPLAINCE WITH NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | |
| | |
| | 5) SHEET 1.0 A AND ALL OTHER APPLICABLE SHEETS - A |
| | BOILER AND BOLIER ROOM IS INDICATED. NO BOILER |
| | INFORMATION, SPEC/EQUIPMENT SHEETS ARE PROVIDED |
| | |
| | PLEASE PROVIDE A NOTE THAT THE BOILER INSTALLATION |
| | SHALL BE UNDER SEPARATE PERMIT. |
| | |
| | PLEASE PROVIDE A NOTE INDICATING THE BOILER |
| | INSTALLATION SHALL COMPPLY WITH THE REQUIRMENTS OF NFPA |
| | 85, BOILER AND COMBUSTION SYSTEMS HAZARDS CODE. |
| | |
| | |
| | |
| | 6) SHEET 1.4 A - A BOILER IS INDICATED WITHIN A 2 HOUR |
| | RATED FIRE WALL ENCLOSURE. THE EXTERIOR WALL IS NOT |
| | INDICATED AS HAVING ANY RATING. THE EXTERIOR WALL LIES |
| | DIRECTLY OPPOSITE A PARKING LOT AND AN AREA DEFINED AS |
| | LEADING TO A PUBLIC WAY FOR AN ADJACENT BUILDING EXIT. |
| | THE EXTEIOR WALL SHALL HAVE THE SAME RATING AS THE |
| | OTHER WALLS SURROUNDING THE BOILER. |
| | |
| | PER NFPA 101, CHAPTER 12 |
| | |
| | 12.3.2.1 SERVICE EQUIPMENT, HAZARDOUS OPERATIONS OR |
| | PROCESSES, AND STORAGE FACILITIES. |
| | 12.3.2.1.1 ROOMS CONTAINING HIGH-PRESSURE BOILERS, |
| | REFRIGERATING MACHINERY OF OTHER THAN THE DOMESTIC |
| | REFRIGERATOR TYPE, LARGE TRANSFORMERS, OR OTHER SERVICE |
| | EQUIPMENT SUBJECT TO EXPLOSION SHALL MEET BOTH OF THE |
| | FOLLOWING REQUIREMENTS: |
| | (1) SUCH ROOMS SHALL NOT BE LOCATED DIRECTLY UNDER OR |
| | ABUTTING REQUIRED EXITS. |
| | (2) SUCH ROOMS SHALL BE SEPARATED FROM OTHER PARTS OF |
| | THE BUILDING BY FIRE BARRIERS IN ACCORDANCE WITH |
| | SECTION 8.3 HAVING A MINIMUM 1-HOUR FIRE RESISTANCE |
| | RATING OR SHALL BE PROTECTED BY AUTOMATIC EXTINGUISHING |
| | SYSTEMS IN ACCORDANCE WITH SECTION 8.7. |
| | |
| | 8.7 SPECIAL HAZARD PROTECTION. |
| | 8.7.1 GENERAL. |
| | 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF |
| | HAZARD GREATER THAN THAT NORMAL TO THE GENERAL |
| | OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE |
| | PROVIDED BY ONE OF THE FOLLOWING MEANS: |
| | (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT |
| | WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN |
| | ACCORDANCE WITH SECTION 8.3 |
| | (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING |
| | SYSTEMS IN ACCORDANCE WITH SECTION 9.7 |
| | (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD |
| | IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 |
| | THROUGH 43. |
| | |
| | PLEASE PROVIDE THE RATING OF THE EXTERIOR WALL THAT |
| | PROTECTS THE EXTERIOR PUBLIC WAY. |
| | |
| | |
| | |
| | |
| | 7) SHEET 1.0 A - DOOR # 5 IS INDICATED WITHIN A 2 HOUR |
| | WALL. DOORS CONTAINED WITH A FIRE RATED WALL SHALL HAVE |
| | AUTOMATIC DOOR CLOSERS. THE DOOR SCHEDULE DOES NOT |
| | INDICATE A DOOR CLOSER FOR DOOR # 5. |
| | |
| | 8.7.1.3 DOORS IN BARRIERS REQUIRED TO HAVE A FIRE |
| | RESISTANCE RATING SHALL HAVE A MINIMUM ?-HOUR FIRE |
| | PROTECTION RATING AND SHALL BE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING IN ACCORDANCE WITH 7.2.1.8. |
| | |
| | |
| | PLEASE CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | 8) SHEET 1.0 A - THE BOLIER IS AN EXPOSION HAZARD. |
| | |
| | 8.7.2* EXPLOSION PROTECTION. WHERE HAZARDOUS PROCESSES |
| | OR STORAGE IS OF SUCH A CHARACTER AS TO INTRODUCE AN |
| | EXPLOSION POTENTIAL, AN EXPLOSION VENTING SYSTEM OR AN |
| | EXPLOSION SUPPRESSION SYSTEM SPECIFICALLY DESIGNED FOR |
| | THE HAZARD INVOLVED SHALL BE PROVIDED. |
| | |
| | |
| | PLEASE PROVIDE OR EXPLAIN/CLARIFY. |
| | |
| | |
| | 9) SHEET 1.0 A AND ALL OTHER APPLICABLE SHEETS - A |
| | FERMENTATION ROOM (INDUSTRIAL) IS INDICATED ALONG WITH |
| | STORAGE (STORAGE) IN THE SAME ROOM WITH NO SEPARATION |
| | FROM THE ASSEMBLY. IS THIS A MIXED OCCUPANCY, SEPARATED |
| | OCCUPANCY OR MULTIPLE OCCUPANCY CLASSIFICATION? |
| | |
| | PLEASE EXPLAIN OR CLARIFY. PROVIDE FOR THE APPLICABLE |
| | OCCUPANCY SEPARATION OF EACH AREA AND/OR PROVIDE FOR |
| | THE REQUIRERMENTS OF THE MOST RESTRICTIVE OCCUPANCY. A |
| | MIXED NONSEPARATED OCCUPANY WILL REQUIRE AN 1 HOUR |
| | SEPARATION OR FIRE SPRINKLER PROTECTION. |
| | |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |