Plan Review Notes
Plan Review Notes For Permit 16120091
Permit Number 16120091
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-08 13:20:51PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22, 110.24
  
 PROVIDE HIGH LEG IDENTIFICATION AT THE ELECTRICAL
 SERVICE AND PANEL BOARDS. NEC 408.3, 10.15, 230.56
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.1, 220.40
  
 PROVIDE WIRE WAY SIZE FOR FEEDERS. NEC 376
  
 PROVIDE A DIMENSIONED DETAIL FOR THE ELECTRIC EQUIPMENT
 SHOWING THE LOCATION AND ALL SAFETY CLEARANCES WITH
 ADEQUATE HEAD ROOM. NEC 110.26
  
 PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL
 SERVICE. NEC 250.94
  
 PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES
 ON THE ROOF. NEC 210.8, 210.63
  
 PROVIDE CIRCUITRY DETAIL FOR EMERGENCY/EXIT LIGHTING.
 NEC 700.12(F)(4)
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405
  
 PROVIDE OCCUPANCY SENSORS AS REQUIRED. FBC C405
  
 PANEL B AND PANEL C ARE NOT LABELED CORRECTLY. THE BREW
 HOUSE PANEL NOT LABELED OR NOT SHOWN. PANEL SCHEDULES
 DO NOT INCLUDE THE KETTLE PUMP AND HOT LIQUOR PUMP. THE
 TANKLESS WATER HEATER SEEMS TO BE MISSING FROM THE
 LAYOUT AT BAR.
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS
  