| 2016-12-08 13:20:51 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE |
| | ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| | MEANS. NEC 110.16, 110.22, 110.24 |
| | |
| | PROVIDE HIGH LEG IDENTIFICATION AT THE ELECTRICAL |
| | SERVICE AND PANEL BOARDS. NEC 408.3, 10.15, 230.56 |
| | |
| | PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.1, 220.40 |
| | |
| | PROVIDE WIRE WAY SIZE FOR FEEDERS. NEC 376 |
| | |
| | PROVIDE A DIMENSIONED DETAIL FOR THE ELECTRIC EQUIPMENT |
| | SHOWING THE LOCATION AND ALL SAFETY CLEARANCES WITH |
| | ADEQUATE HEAD ROOM. NEC 110.26 |
| | |
| | PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL |
| | SERVICE. NEC 250.94 |
| | |
| | PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES |
| | ON THE ROOF. NEC 210.8, 210.63 |
| | |
| | PROVIDE CIRCUITRY DETAIL FOR EMERGENCY/EXIT LIGHTING. |
| | NEC 700.12(F)(4) |
| | |
| | PROVIDE INTERIOR LIGHTING CALCULATION SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY |
| | CONSERVATION REQUIREMENTS. FBC C405 |
| | |
| | PROVIDE OCCUPANCY SENSORS AS REQUIRED. FBC C405 |
| | |
| | PANEL B AND PANEL C ARE NOT LABELED CORRECTLY. THE BREW |
| | HOUSE PANEL NOT LABELED OR NOT SHOWN. PANEL SCHEDULES |
| | DO NOT INCLUDE THE KETTLE PUMP AND HOT LIQUOR PUMP. THE |
| | TANKLESS WATER HEATER SEEMS TO BE MISSING FROM THE |
| | LAYOUT AT BAR. |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM |
| | SYSTEMS, SECURITY AND DATA SYSTEMS |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |