Plan Review Notes
Plan Review Notes For Permit 16120091
Permit Number 16120091
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-07 09:05:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120091
 ADD: 332 EVERNIA ST.
 CONT: MONTEIRO DEVELOPMENT INC.
 TEL: 561-346-6916
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 07/2016
 ACTION: DENIED
  
 1) THE COVERSHEET C-1 LIST THIS PROJECT AS A LEVEL II
 ALTERATION. PLEASE BE AWARE THE LAST KNOWN USE OF THIS
 SPACE WAS A GYM AN A3 OCCUPANCY. THIS IS A CHANGE OF
 USE WITHIN THE SAME OCCUPANCY GROUP TO AN A2 TAVERNS
 AND BARS. PLEASE UPDATE THE PLANS TO THE REQUIREMENTS
 OF SECTION 1001.3 CHANGE OF OCCUPANCY CLASSIFICATION,
 THE 2014 EXISTING BUILDING CODE.
 EXISTING BUILDING CODE 1001.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 1002
 THROUGH 1012 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 2) PLEASE NOTE THERE IS A DISCREPANCY IN THE OCCUPANT
 LOAD PROVIDED. THE COVERSHEET DECLARES 173 OCCUPANTS
 WHEREAS THE LIFE SAFETY SHEET 1.4A LIST 178 AS A TOTAL
 OCCUPANT LOAD. PLEASE UPDATE THE DISCREPANCY.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 3) PLEASE ALSO NOTE THE LIFE SAFETY SHEET 1.4AINTHE
 OCCUPANT LOAD EXITING IS USING THE MORE RESTRICTIVE
 FACTOR 0.3 INCHES FOR STAIRS SEE FBC-B 1005.3.1. THE
 ACTUAL COUNT ALLOWED WILL BE LOWER.
  
 4) THE REAR EXIT DOORWAY HAS A HALLWAY IN FRONT OF IT 4
 FT. 7 INCHES WIDE OR 55 INCHES IN WIDTH. DOOR & 10
 SWINGS OVER THE ? OF THE REQUIRED EXIT WIDTH. THE
 REQUIRED MINIMUM EXIT FOR OCCUPANT LOADS OF 50 OR MORE
 44 INCHES, ? OF THE REQUIRED WIDTH IS 22 INCHES. WITH
 THE DOOR IN THE OPEN POSITION ONLY 19 INCHES REMAIN.
 2014 FBC-B 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED,
 SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7
 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE
 THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 5) 2014 EXISTING BUILDING CODE SECTION 1013 ENERGY
 CONSERVATION SHALL COMPLY WITH THE FLORIDA BUILDING
 CODE, ENERGY CODE, PLEASE PROVIDE HOW COMPLIANCE WILL
 BE ACHIEVED.
  
 6) PLEASE PROVIDE COMPLIANCE WITH 2014 EXISTING
 BUILDING CODE 1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
 6A) 1012.2.1 FIRE SPRINKLER SYSTEM.
 6B) 1012.2.2 FIRE ALARM AND DETECTION SYSTEM.
 7) PLEASE SHOW HOW COMPLIANCE WITH SECTION 1012.1.4
 ACCESSIBILITY OF THE 2014 EXISTING BUILDING CODE IS
 ACHIEVED. ALL BUILDINGS UNDERGOING A CHANGE OF
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 1012.8 EXIST. BUILD. CODE. PLEASE SHOW ON THE LIFE
 SAFETY PLAN A1.4A.
  
 7A) DINING SURFACES. 226.1. WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 7B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 7C) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 7D) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 8) THE COVER SHEET INDICATES IN THE REAR OF THE
 BUILDING THERE WILL BE NEW OVERHEAD DOOR AND REAR SWING
 EGRESS DOORS. SHEET A1.6A SHOWS A DETAIL OF AN EXISTING
 HEADER. GOOGLE SHOWS THE REAR OF THE BUILDING WITH A
 SINGLE 3-0X 7-0 DOOR. PLEASE EXPLAIN EXISTING HEADER.
 IN THIS REVIEW THERE WERE NO STRUCTURAL PLANS
 INDICATING HOW THE MWFRS( MAIN WIND FORCE RESISTING
 SYSTEM) IS GOING TO REMAIN INTACT WITH THE NEW
 OPENINGS, IF LINTELS OR CONCRETE BEAMS TYPE OF COLUMNS,
 ARE GOING TO BE CREATED. THERE IS NO SIZING INFORMATION
 OF REBAR, HOOPS, SPACING OF HOOPS, STRENGTH OF CONCRETE
 MIX LAP SPLICES, REBAR EMBEDMENT TO EXISTING FOOTERS
 AND BEAMS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 EXTERIOR ELEVATIONS.
 WALL SYSTEMS NEW WALL OPENINGS
 ROOF SYSTEMS NEW OPENINGS.
  
 9) THE COVERSHEET C.1 INDICATES ON THE FRONT OF THE
 BUILDING NEW SOLAR INNOVATION BIFOLD WINDOWS, SHEET
 1.6A THE NEW ELEVATIONS SHOW THE REMOVAL OF A DOORWAY
 AND INFILL OF SILL. THE NEW SILL HAS NO DETAILS HOW IT
 WILL ANCHORED AS PART OF THE MWFRS (MAIN WIND FORCE
 RESISTING SYSTEM) TO ANCHOR THE BIFOLD WINDOWS.
 1609.6.4. MAIN WIND FORCE-RESISTING SYSTEMS.
  
 10) SHEET 1.0A THE DIMENSIONED FLOOR PLAN SHOWS NEW
 DUMPSTER ENCLOSURE RAISED EXIT DISCHARGE LANDING SWITCH
 BACK AND RAMP WITH EITHER GUARDS OR HANDRAILS. THERE IS
 NO STRUCTURAL INFORMATION FOR ANY OF THESE ELEMENTS,
 SIZE OF FOOTERS, IF MONOLITHIC OR STEMWALL,
 REINFORCEMENT OF REBARS, FOR FOOTERS, COLUMNS, AND
 BEAMS. NO NOTATION AS TO WHERE THE REAR PROPERTY LINE
 IS LOCATED ON THE PLANS, NOR POWER POLE LOCATION NOR
 THE REROUTING OF THE SOUTHEAST RAIN DOWNSPOT.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING STRUCTURAL ELEMENTS, FOOTERS,
 SLABS, COLUMNS AND BEAMS
 1010.8.2 OUTDOOR CONDITIONS. OUTDOOR RAMPS AND OUTDOOR
 APPROACHES TO RAMPS SHALL BE DESIGNED SO THAT WATER
 WILL NOT ACCUMULATE ON WALKING SURFACES.
  
 1010.9 HANDRAILS. RAMPS WITH A RISE GREATER THAN 6
 INCHES (152 MM) SHALL HAVE HANDRAILS ON BOTH SIDES.
 HANDRAILS SHALL COMPLY WITH SECTION 1012.
 11) SHEET 1.0A THE REAR EXIT DOOR # 6 DOES SHOW A
 REQUIRED PANIC BAR AND DOOR CLOSER ON THE NEW EXIT
 DOOR. WITH THIS TYPE OF HARDWARE ON THE DOOR A 12 INCH
 MANEUVERING CLEARANCE IS REQUIRED ON THE INTERIOR OF
 THE DOOR. SEE 2014 ACCESS. CODE FIGURE 404.2.4.1.
  
 12) SHEET 1.0A THE REAR EXIT DOOR # 6 DOES SHOWS A
 UPPER LANDING FOR A RAMP. THE LANDING DOES NOT GIVE A
 DIMENSION FOR WIDTH FROM THE BUILDING. PLEASE SHOW
 COMPLIANCE WITH ACCESS. CODE 405.7.4 CHANGE IN
 DIRECTION.
  
 13) SHEET 3.4M SHOWS ROOF TOP EQUIPMENT. RTU 1 IS NOT
 CLEAR IF THIS UNIT IS EXISTING OR NEW. DETAILS SHOW 3X3
 ANGLES TO BE WELDED TO THE TOP CHORD OF THE BAR JOIST,
 THERE IS NO INFORMATION AS TO THE TYPE OF WELDS, THE
 3X3 ANGLES DOES NOT PROVIDE THE THICKNESS NOR THE
 LENGTH OF THE ANGLES. THE DESIGNER HAS NOT INDICATED
 POINT LOADING OF THE BAR JOIST AND OR STRENGTHENING OF
 BAR JOIST FOR THE ADDITIONAL LOADING.
 THE ROOF TOP CURB SIZE IS NOT PROVIDED, NOR PRODUCT
 APPROVALS FOR THE CURB WERE SUBMITTED.
 MISSING INFORMATION. ADMINISTRATIVE CODE 107.2.1.3.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 14) SHEET 3.4M ALSO SHOWS A CONNECTION FOR THE ROOF TOP
 RTU TO THE CURB, THIS DETAIL DOES NOT PROVIDE THE WIND
 SPEED THAT IT WAS DESIGNED FOR. 2014 FBC-M- 301.15 WIND
 RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 15) SHEET 3.4M . PLEASE PROVIDE THE MEAN ROOF HEIGHT TO
 SEE IF COMPLIANCE WITH SECTION 1509.6.4 OF THE FBC-B
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT
 A HEIGHT EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL
 BE PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS,
 THE EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL
 TO THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) HIGH OR
 WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
  
 16) SHEET 3.4M DOES SHOW NEW ROOF TOP EQUIPMENT CLOSER
 THAN 10 FEET FROM THE EDGE OF THE ROOF, PLEASE SHOW
 COMPLIANCE WITH SECTION 1013.6 MECHANICAL EQUIPMENT OF
 THE FBC-B.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
 PLEASE ALSO NOTE GOOGLE SHOWS (2) ROOFTOP UNITS AT THE
 REAR OF THE BUILDING WITHIN 10 FEET OF THE EDGE OF THE
 ROOF.
  
 17) IF MECHANICAL SCREENS ARE REQUIRED BY OTHER CODES
 OR DEPARTMENTS THEN THEY ARE TO BE DESIGNED FOR THIS
 WIND SPEED AND ELEVATION AND ALSO IN COMPLIANCE WITH
 ? 1509.6 MECHANICAL EQUIPMENT SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 18) SHEET 3.4M ALSO SHOWS NEW ROOF TOP A/C STANDS.
 PRODUCT APPROVALS FOR ROOF TOP STANDS MUST SHOW ALL
 TABLES WITHIN THE PRODUCT APPROVAL TO BE IDENTIFIED
 THAT ARE PERTINENT TO THE INSTALLATION, THEN REVIEWED
 BY THE DESIGNER OF RECORD.
  
 19) SHEET 3.4M. MISSING ROOF TOP WIND DESIGN CRITERIA
 2014 FBC-B 1603.1.4.
  
 20A) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 20B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 22) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  