Plan Review Notes
Plan Review Notes For Permit 16120057
Permit Number 16120057
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-12 14:11:481ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1] BOND LOW VOLTAGE METAL RACKS WITH MINIMUM 6 AWG. NEC
 645.15, 250.134-136.