| 2016-12-16 15:13:37 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET G-GEN7 - AN AREA FOR CONTRACTOR TRAILERS IN |
| | INDICATED ON A NOTE. |
| | |
| | CONSTRUCTION, DEMOLITION, AND RENOVATION SHALL COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. |
| | |
| | A PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER |
| | RELATED TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE |
| | 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE |
| | REQUIRED IN EACH TRAILER. |
| | 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER |
| | CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH |
| | AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER |
| | FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS |
| | HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE |
| | IN ACCORDANCE WITH TABLE 4.2.1. |
| | |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | NOTES: |
| | (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY |
| | STRUCTURES IS LESS THAN THE MINIMUM SEPARATION |
| | DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE |
| | CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING |
| | WALL LENGTHS OF THE TEMPORARY STRUCTURES. |
| | (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES |
| | SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL |
| | STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO |
| | MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE |
| | APPLYING THIS TABLE, IS 3600 MM (144 IN.). |
| | |
| | 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES, |
| | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND |
| | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION. |
| | |
| | PLEASE PROVIDE A NOTE OF COMPLAINCE AND ACKNOWLEDGEMENT |
| | OR THE ABOVE REQUIRMENTS. |
| | |
| | |
| | 2) SHEET A-SCBG1 - THE SCEENING BLDG MAY BE CLASSIFIED |
| | A U OCCUPANCY WITHIN THE FL BLDG CODE; HOWEVER, IT |
| | APPEARS TO BE A STORAGE OCCUPANCY UNDER THE FLORIDA |
| | FIRE PREVENTION CODE. |
| | |
| | NFPA 42, STORAGE OCCUPANCY |
| | |
| | 42.2.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN |
| | ACCORDANCE WITH SECTION 7.8. |
| | |
| | |
| | 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 |
| | THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. 7.8.1.2 |
| | ILLUMINATION OF MEANS OF EGRESS SHALL BE CONTINUOUS |
| | DURING THE TIME THAT THE CONDITIONS OF OCCUPANCY |
| | REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE FOR USE, |
| | UNLESS OTHERWISE PROVIDED IN |
| | 7.8.1.2.2. |
| | |
| | PLEASE PROVIDE THE ABOVE REQUIREMENT. |
| | |
| | |
| | |
| | 3) SHEET A-SCBG1 - THE SCEENING BLDG MAY BE CLASSIFIED |
| | A U OCCUPANCY WITHIN THE FL BLDG CODE; HOWEVER, IT |
| | APPEARS TO BE A STORAGE OCCUPANCY UNDER THE FLORIDA |
| | FIRE PREVENTION CODE. |
| | |
| | 42.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE |
| | PROVIDED IN NORMALLY OCCUPIED STORAGE OCCUPANCIES IN |
| | ACCORDANCE WITH SECTION 7.9, EXCEPT FOR SPACES OCCUPIED |
| | ONLY DURING DAYLIGHT HOURS WITH NATURAL ILLUMINATION IN |
| | ACCORDANCE WITH 42.2.8.2. |
| | 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10. |
| | |
| | PLEASE PROVIDE THE ABOVE REQUIREMENT. |
| | |
| | |
| | 4) SHEET A-SCBG1 - THE SCEENING BLDG MAY BE CLASSIFIED |
| | A U OCCUPANCY WITHIN THE FL BLDG CODE; HOWEVER, IT |
| | APPEARS TO BE A STORAGE OCCUPANCY UNDER THE FLORIDA |
| | FIRE PREVENTION CODE. |
| | |
| | 7.10 MARKING OF MEANS OF EGRESS. |
| | 7.10.1 GENERAL. |
| | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| | MARKED IN ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED |
| | IN CHAPTERS 11 THROUGH 43. |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS, |
| | SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY |
| | VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. |
| | |
| | PLEASE PROVIDE THE ABOVE REQUIREMENT. |
| | |
| | |
| | 5) THE DOOR SCHEDULE DOES NOT INDICATE THE TYPE OF EXIT |
| | HARDWARE, LATCH AND/OR HANDLE OPERATION TYPE. |
| | |
| | 42.2.2.2 DOORS. |
| | 42.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.1 DOOR OPENINGS. |
| | 7.2.1.1 GENERAL. |
| | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| | CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND |
| | TO THE SPECIAL REQUIREMENTS OF 7.2.1. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | |
| | PLEASE PROVIDE FOR THE ABOVE REQUIREMENTS. |
| | |
| | |
| | |
| | 6) A LIFE SAFETY PLAN DOES NOT APPEAR TO BE PROVIDED |
| | REGARDING THE GRIT REMOVAL AND PRE-TREATMENT STRUCTURES |
| | SHOWING PATHS OF TRAVEL THROUGH GRATINGS, STAIRS AND |
| | GAURDRAIL SYSTEMS. |
| | |
| | PLEASE PROVIDE A LIFE SAFETY PLAN THAT OUTLINES ALL |
| | PEDESTRIAN WAYS, EXIT ACCESS, AND EXIT DISCHARGES TO A |
| | PUBLIC WAY, INCLUDING MARKING OF THE MEANS OF EGRESS, |
| | ILLUMINATION OF THE EXIT TRAVEL PATHS, AND INCLUDE ANY |
| | GATES ALONG THE PATH AND DIRECTIONAL INDICATORS. |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |