| 2016-12-27 11:33:31 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. E1.00-1.01- GENERAL NOTES TO CONSTRUCTION DOCUMENTS: |
| | PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ALL SITE LIGHTING AND ASSOCIATED |
| | EQUIPMENT, TEMPORARY GENERATOR USE, ALL LOW VOLTAGE |
| | SYSTEMS TO INCLUDE BUT NOT LIMITED TO, CCTV, PHONE AND |
| | DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. |
| | 2. PROVIDE A GENERAL NOTE TO INDICATE REQUIREMENTS TO |
| | MAINTAIN BURIAL DEPTHS PER NEC 300.5 TO ALL SITE |
| | REWORK. |
| | 3. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, |
| | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP |
| | AND COMPLETIONS DOCUMENTS. |
| | 4. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING |
| | REQUIREMENTS. |
| | 5. PLEASE SHOW REVISED AIC CALCULATION BASED ON |
| | INFORMATION PROVIDED BY FPL UTILITY FOR APPROVAL. NEC |
| | 110.24 FBC 107. |
| | 6. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING |
| | 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |