| 2016-12-21 15:20:28 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16120051 |
| | ADD: 4375 EASLEY DR. IMPROVEMENTS TO THE HEADWORKS |
| | STRUCTURE |
| | CONT: TBD |
| | TEL: 954-609-1525 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 21/ 2016 |
| | ACTION: DENIED |
| | |
| | 1A) THE COVERSHEET INDICATES THE SUBMITTED PLANS ARE |
| | VOLUME 2 OF 2. WHERE IS VOLUME 1 OF 2? IT WOULD APPEAR |
| | ONLY ? OF THE PLANS WERE SUBMITTED? 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1B) THE PLANS INDICATE THE SUBMITTED PLANS ARE FOR |
| | PERMIT SET NOT CONSTRUCTION, IS THERE GOING TO BE A |
| | DIFFERENT SET OF PLANS TO BUILD THE STRUCTURE? IF SO |
| | THEY WILL NEED TO BE REVIEWED AND APPROVED. 107.3.1 |
| | APPROVAL OF CONSTRUCTION DOCUMENTS. WHEN THE BUILDING |
| | OFFICIAL ISSUES A PERMIT, THE CONSTRUCTION DOCUMENTS |
| | SHALL BE NOTED, IN WRITING OR BY STAMP, AS ?REVIEWED |
| | FOR CODE |
| | COMPLIANCE.? ONE SET OF CONSTRUCTION DOCUMENTS SO |
| | REVIEWED SHALL BE RETAINED BY THE BUILDING OFFICIAL. |
| | THE OTHER SET SHALL BE RETURNED TO THE APPLICANT, SHALL |
| | BE KEPT AT THE SITE OF WORK AND |
| | SHALL BE OPEN TO INSPECTION BY THE BUILDING OFFICIAL OR |
| | A DULY AUTHORIZED REPRESENTATIVE. |
| | |
| | 2) PLEASE NOTE ONLY (1) ORIGINAL SIGNED AND SEALED |
| | SOILS REPORT WAS SUBMITTED. 2014 FLORIDA BUILDING CODE |
| | W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION SECTION 107.1 SUBMITTAL |
| | DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS, |
| | STATEMENT OF SPECIAL INSPECTIONS, GEOTECHNICAL REPORT |
| | AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS |
| | WITH EACH PERMIT APPLICATION. |
| | |
| | 3) THE PLANS AFFILIATED WITH THE SCREENS |
| | STRUCTURE(S-SCRN) AND THE GRIT REMOVAL STRUCTURE |
| | (S-GRT) SHOW MASSIVE CONCRETE RESTORATION WORK. SHEET |
| | S-GEN-2 STRUCTURAL OBSERVATIONS INDICATES THERE IS TO |
| | BE AN ENGINEER ONSITE FOR QUALITY INSURANCE |
| | INSPECTIONS. THE CITY BELIEVES THIS PROJECT WOULD BEST |
| | BE SUITED WITH AN ONSITE RESIDENT INSPECTOR. IF THE |
| | CONTRACTOR AND OR OWNERS REPRESENTATIVE WOULD LIKE THE |
| | RESIDENT INSPECTOR TO ALSO COMPLETE THE STRUCTURAL |
| | INSPECTIONS FOR THE NEW SCREENINGS BUILDING, THEN LIST |
| | BOTH PERMIT NUMBERS ON THE RESIDENT INSPECTOR FORM. |
| | 3A) ONCE A CONTRACTOR HAS BEEN SELECTED RESIDENT |
| | INSPECTOR FORMS WILL BE E-MAILED TO THEM SO ALL PARTIES |
| | INVOLVED WILL BE ABLE TO SIGN THE RESIDENT INSPECTOR |
| | AGREEMENT. IF THERE IS ANY OTHER REPRESENTATIVE THAT |
| | WOULD LIKE THE RESIDENT INSPECTOR FORMS E-MAILED, |
| | PLEASE CONTACT ME BY E-MAIL. E-MAIL [email protected]. |
| | RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES |
| | NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT. |
| | |
| | 3B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. |
| | |
| | 3C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 3D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 3E) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND |
| | GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | RESIDENT INSPECTORS. COMMENT # 14. THREE (3) COPIES OF |
| | ALL SHOP DRAWINGS (HANDRAILS, PRECAST JOINT AND SLABS, |
| | PRODUCT APPROVALS, TRUSSES, BAR JOIST, ETC.) MUST BE |
| | SUBMITTED TO THE BUILDING DEPARTMENT. TWO REVIEWED SETS |
| | OF DOCUMENTS WILL BE RETURNED TO THE JOB SITE BEFORE |
| | ANY OF THE ABOVE ARE INSTALLED ON THE JOB. |
| | |
| | 3F) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 4) THIS 1ST REVIEW NO PRODUCT INFORMATION WAS SUBMITTED |
| | FOR THE PRODUCTS THAT WILL BE USED IN THE CONCRETE |
| | RESTORATION NOR THE VARIOUS COATING SYSTEMS TO BE USED |
| | IN THE PROCESS. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5) SHEET S-SCRN-2 IT WOULD APPEAR THAT THERE WILL BE |
| | BOTTOM OF SLAB PENETRATIONS WHERE NEW SLABS ARE BEING |
| | POURED BELOW THE EXISTING LEVELS. THE SOILS REPORT |
| | INDICATES THE WATER LEVEL IS APPROXIMATELY 10 FEET |
| | BELOW GRADE. PLEASE PROVIDE A DE-WATERING PLAN. THE |
| | RADISE SOILS REPORT RECOMMENDS UNDER THE HEADING 7.5 |
| | THE DEWATERING SYSTEM EMPLOYED SHOULD BE CAPABLE OF |
| | MAINTAINING A PRE-DRAINED SURFACE A MINIMUM OF 24 |
| | INCHES BELOW THE EXCAVATED BOTTOMS. PLEASE PROVIDE |
| | DOCUMENTATION HOW THE EXCAVATED AREAS TO BE CONCRETED |
| | ARE GOING TO BE KEPT DRY FOR SUITABLE BEARING VALUES. |
| | 1803.6 REPORTING. (5) RECOMMENDATIONS FOR FOUNDATION |
| | TYPE AND DESIGN CRITERIA, INCLUDING BUT NOT LIMITED TO: |
| | BEARING CAPACITY OF NATURAL OR COMPACTED SOIL; |
| | MITIGATION OF THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL |
| | SETTLEMENT AND VARYING SOIL STRENGTH; AND THE EFFECTS |
| | OF ADJACENT LOADS. |
| | |
| | 6) SHEET S-GEN-2 INDICATES ITEMS THAT ARE TO BE |
| | DEFERRED SUBMITTALS. |
| | 6A) PRECAST CONCRETE UNITS |
| | 6B) ATTACHMENT OF MECHANICAL UNITS TO SUPPORTS |
| | 6C) ATTACHMENT OF PROCESS UNIT/ EQUIPMENT TO SUPPORT |
| | 6D) SPECIALTY CONSTRUCTION OF PIPE SUPPORTS |
| | |
| | NOTE IF THE ABOVE SUBMITTALS ARE TO BE BY A DELEGATE |
| | ENGINEER PLEASE REVIEW: 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |