2019-04-15 07:47:35PLUMBING PROVISO:
  
 SHALL COMPLY PRIOR TO FINAL INSPECTION.
  
 1. PROVIDE ISOMETRIC DRAWING FOR THE FLOOR DRAIN. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. A TRAP PRIMER IS REQUIRED ON THE FLOOR DRAIN. FBC PL
 1002.4.1
  
 3. A VENT IS REQUIRED FOR THE FLOOR DRAIN. FBC ACC
 901.2.1
  
  
  