| Plan Review Notes For Permit 16120034 |
| Permit Number |
16120034 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-12 09:21:26 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO | | | | | | 1] FBC-E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. |
|