2016-12-07 11:16:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16111265
 12/7/16
  
 1) THE RESIDENTIAL ENERGY COMPLIANCE FORM R405-2015
 CANNOT BE USED ON A COMMERCIAL BUILDING. PLEASE SEE
 DEFINITIONS OF RESIDIENTIAL AND COMMERCIAL IN SECTIONS
 C202 & R202 FBC-14 ENERGY CONSERVATION. RESIDENTIAL
 CLASSIDICATION IS LIMITED TO THREE STORIES. THE
 BUILDING BEING RENOVATED IS FOUR STORIES.
  
 2) SUBMIT AC CHANGEOUT FORMS FOR THE REPLACED SYSTEMS.
 THE FORMS CAN BE FOUND ON THE DEVELOPMENT SERVICES
 WEBSITE- WWW.CITYOFWPB.COM.
  
 3) SHEET M2.3: THE 8X6 TRANSFER DUCTS IN THE
 THREE-BEDROOM UNITS ARE UNDERSIZED PER SECTION
 601.5.(1).
  
 4) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR
 ANCHORING THE NEW CONDENSERS TO THE EXISTING STANDS-
 SECTION 301.15.
  