| Plan Review Notes For Permit 16111261 |
| Permit Number |
16111261 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2017-08-25 13:54:41 | 1) SHT. P1.1 - PLUMBING NOTES - THERE IS A NOTE STATING | | | THAT PVC IN THE PLENUM CLOSET IS TO BE WRAPPED WITH | | | PLENUM RATED ARMAFLEX. PVC IS NOT RATED FOR USE WITHIN | | | A PLENUM. THE ARMAFLEX MAY BE APPROVED FOR USE IN A | | | PLENUM BUT THE PVC WITHIN THE PLENUM IS STILL A | | | VIOLATION. THE ARMAFLEX DOES NOT PROTECT THE PVC FROM | | | IGNITION AND DOES NOT MEET THE INTENT OF THE CODE. | | | COMPLY WITH 2014 FBC - MECHANICAL SEC.602.2. | | | 2) REMOVE SHEETS P3.8 & P3.9 AS NOTED IN NARRATIVE FROM | | | DESIGN PROFESSIONAL. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|