2017-08-25 13:54:411) SHT. P1.1 - PLUMBING NOTES - THERE IS A NOTE STATING
 THAT PVC IN THE PLENUM CLOSET IS TO BE WRAPPED WITH
 PLENUM RATED ARMAFLEX. PVC IS NOT RATED FOR USE WITHIN
 A PLENUM. THE ARMAFLEX MAY BE APPROVED FOR USE IN A
 PLENUM BUT THE PVC WITHIN THE PLENUM IS STILL A
 VIOLATION. THE ARMAFLEX DOES NOT PROTECT THE PVC FROM
 IGNITION AND DOES NOT MEET THE INTENT OF THE CODE.
 COMPLY WITH 2014 FBC - MECHANICAL SEC.602.2.
 2) REMOVE SHEETS P3.8 & P3.9 AS NOTED IN NARRATIVE FROM
 DESIGN PROFESSIONAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW