| Date |
Text |
| 2017-06-28 05:13:02 | 1) SHOW THE DIMENSIONS (LXW) OF THE REQUIRED CLEAR |
| | FLOOR SPACE FOR THE WATER CLOSETS, LAVATORIES, KITCHEN |
| | SINKS & SHOWERS IN THE UFAS UNITS. THE REQUIRED CLEAR |
| | FLOOR SPACE FOR THE FIXTURES SHALL COMPLY WITH UFAS |
| | SECS.4.34.5.2 THROUGH 4.34.6.5. |
| | 2) SUBMIT DETAILS FOR THE REQUIRED REINFORCEMENT FOR |
| | GRAB BARS FOR THE WATER CLOSETS & SHOWERS. COMPLY WITH |
| | UFAS SECS. 4.34.5.2 (3), 4.34.5.5 (3) & FIGURES 47 (B) |
| | & FIG. 49. SHOW THE MINIMUM AND MAXIMUM MEASUREMENTS |
| | FROM THE FLOOR AND THE MINIMUM LENGTHS AND DIMENSIONS |
| | OF THE REINFORCING ON SHTS. A5.2, A5.3 & A5.4. |
| | 3) SUBMIT AN ELEVATION DETAIL OF THE HILO DRINKING |
| | FOUNTAIN.COMPLY WITH UFAS SECS. 4.1.6, 4.4.1.2, 4.15. |
| | 4) SHT.A5.4 - DETAIL #1 - SHOW THE DIMENSIONS OF THE |
| | CLEAR FLOOR SPACES REQUIRED FOR THE ACCESSIBLE |
| | LAVATORIES AND WATER CLOSETS. |
| | 5) SHT. A5.4 - DETAILS A,B,C & D SHOWS A GRAB BAR IN |
| | THE TOILET ROOM ACCESSIBLE STALL MOUNTED IN THE |
| | VERTICAL POSITION BUT UFAS SEC.4.17.6 AND FIG. (A) SHOW |
| | THE GRAB BARS ONLY IN A HORIZONTAL POSITION. GRAB BARS |
| | INSTALLED IN A VERRTICAL POSITION DO NOT APPEAR TO |
| | COMPLY WITH UFAS. CLARIFY. |
| | 6) SHT. A5.4 - ELEVATION DETAILS "A" & "B" DO NOT |
| | APPEAR TO CORRELATE WITH THE PLAN VIEW ON DETAIL #1 - |
| | CLARIFY. |
| | 7) A6.4 - DETAIL #1 - THE HEIGHT OF THE SINK IN THE |
| | CLUBHOUSE ACTIVITY ROOM SHALL BE A MAXIMUM OF 34 INCHES |
| | ABOVE THE FINISH FLOOR. UFAS SEC. 4.24.2. |
| | 8) SHT. P1.1 - PLUMBING NOTES - THERE IS A NOTE STATING |
| | THAT PVC IN THE PLENUM CLOSET IS TO BE WRAPPED WITH |
| | PLENUM RATED ARMAFLEX. PVC IS NOT RATED FOR USE WITHIN |
| | A PLENUM. SUBMIT TWO COPIES OF MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PLENUM RATED ARMAFLEX AND |
| | DETAILS AS TO HOW THE ARMAFLEX WILL BE INSTALLED ON THE |
| | PVC PIPE.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) SHT. P1.1 - WATER HEATER DETAIL - HEAT TRAPS ARE |
| | REQUIRED ON THE HOT AND COLD WATER LINES OF THE WATER |
| | HEATER. 2014 FBC-ENERGY SEC.C404.4, |
| | 10) SHT. P2.2 - SHUTOFF VALVES ARE REQD. AT THE BASE OF |
| | THE WATER RISERS. 2014 FBC-PLUMBIING SEC.606.1 (4). |
| | 11) SHTS. P3.1, P3.2, P3.3, & P3.5 - THE HUB DRAIN |
| | SHALL CONNECT TO THE SANITARY SYSTEM DOWNSTREAM OF THE |
| | WATER CLOSET. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |