2017-06-28 05:13:021) SHOW THE DIMENSIONS (LXW) OF THE REQUIRED CLEAR
 FLOOR SPACE FOR THE WATER CLOSETS, LAVATORIES, KITCHEN
 SINKS & SHOWERS IN THE UFAS UNITS. THE REQUIRED CLEAR
 FLOOR SPACE FOR THE FIXTURES SHALL COMPLY WITH UFAS
 SECS.4.34.5.2 THROUGH 4.34.6.5.
 2) SUBMIT DETAILS FOR THE REQUIRED REINFORCEMENT FOR
 GRAB BARS FOR THE WATER CLOSETS & SHOWERS. COMPLY WITH
 UFAS SECS. 4.34.5.2 (3), 4.34.5.5 (3) & FIGURES 47 (B)
 & FIG. 49. SHOW THE MINIMUM AND MAXIMUM MEASUREMENTS
 FROM THE FLOOR AND THE MINIMUM LENGTHS AND DIMENSIONS
 OF THE REINFORCING ON SHTS. A5.2, A5.3 & A5.4.
 3) SUBMIT AN ELEVATION DETAIL OF THE HILO DRINKING
 FOUNTAIN.COMPLY WITH UFAS SECS. 4.1.6, 4.4.1.2, 4.15.
 4) SHT.A5.4 - DETAIL #1 - SHOW THE DIMENSIONS OF THE
 CLEAR FLOOR SPACES REQUIRED FOR THE ACCESSIBLE
 LAVATORIES AND WATER CLOSETS.
 5) SHT. A5.4 - DETAILS A,B,C & D SHOWS A GRAB BAR IN
 THE TOILET ROOM ACCESSIBLE STALL MOUNTED IN THE
 VERTICAL POSITION BUT UFAS SEC.4.17.6 AND FIG. (A) SHOW
 THE GRAB BARS ONLY IN A HORIZONTAL POSITION. GRAB BARS
 INSTALLED IN A VERRTICAL POSITION DO NOT APPEAR TO
 COMPLY WITH UFAS. CLARIFY.
 6) SHT. A5.4 - ELEVATION DETAILS "A" & "B" DO NOT
 APPEAR TO CORRELATE WITH THE PLAN VIEW ON DETAIL #1 -
 CLARIFY.
 7) A6.4 - DETAIL #1 - THE HEIGHT OF THE SINK IN THE
 CLUBHOUSE ACTIVITY ROOM SHALL BE A MAXIMUM OF 34 INCHES
 ABOVE THE FINISH FLOOR. UFAS SEC. 4.24.2.
 8) SHT. P1.1 - PLUMBING NOTES - THERE IS A NOTE STATING
 THAT PVC IN THE PLENUM CLOSET IS TO BE WRAPPED WITH
 PLENUM RATED ARMAFLEX. PVC IS NOT RATED FOR USE WITHIN
 A PLENUM. SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATIONS FOR THE PLENUM RATED ARMAFLEX AND
 DETAILS AS TO HOW THE ARMAFLEX WILL BE INSTALLED ON THE
 PVC PIPE.WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHT. P1.1 - WATER HEATER DETAIL - HEAT TRAPS ARE
 REQUIRED ON THE HOT AND COLD WATER LINES OF THE WATER
 HEATER. 2014 FBC-ENERGY SEC.C404.4,
 10) SHT. P2.2 - SHUTOFF VALVES ARE REQD. AT THE BASE OF
 THE WATER RISERS. 2014 FBC-PLUMBIING SEC.606.1 (4).
 11) SHTS. P3.1, P3.2, P3.3, & P3.5 - THE HUB DRAIN
 SHALL CONNECT TO THE SANITARY SYSTEM DOWNSTREAM OF THE
 WATER CLOSET.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  