Plan Review Notes
Plan Review Notes For Permit 16111261
Permit Number 16111261
Review Stop B
Sequence Number 3
Notes
Date Text
2017-06-28 12:56:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1-2. OK
  
 3. FROM PREVIOUS LISTS: KAYKAN SOFFIT PRODUCT APPROVAL,
 INDICATE WHICH PRODUCT AND INSTALLATION METHOD IS
 PROPOSED (DRAWING PAGE 1 OF 15).
  
 2ND REVIEW, THE DOCUMENT SUBMITTED IS NOT A PART OF THE
 PRODUCT APPROVAL. IT APPEARS TO BE AN EVALUATION REPORT
 BUT DOES NOT INCLUDE A PRODUCT APPROVAL NUMBER. ONE
 ITEM IS CIRCLED, 20' MRH, BUT THE APARTMENT BUILDINGS
 ARE FOUR STORIES.
  
 THIS ITEM CAN BE A PROVISO UPON REQUEST - PRIOR TO
 INSTALLATION, SUBMIT PRODUCT APPROVAL WITH INSTALLATION
 METHOD INDICATED.
  
 3RD REVIEW, RESPONSE LETTER STATES THAT IT IS ATTACHED,
 BUT I WAS UNABLE TO LOCATE THIS INFORMATION.
  
 4. OK
  
 5. WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR
 THIS JOB, FBC 105.
  
 6. TEST REPORTS FOR THE FLOORING UNDERLAYMENT WERE NOT
 PROVIDED. "GROUNDWORKS" SPEC SHEET WAS PROVIDED.
  
 PROVIDE TEST REPORTS FOR THE FLOORING UNDERLAYMENT
 ACOUSTIC INSULATION:
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 C. FBC B 720.2 OR 603.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723 (FLAME SPREAD).
  
 3RD REVIEW, RESPONSE LETTER REFERS TO AN EXCEPTION FOR
 COMBUSTIBLE INSULATION BOARDS NOT MORE THAN 1/2"; IT
 APPEARS THAT THE PROPOSED PRODUCT IS A ROLLED PRODUCT,
 NOT BOARDS. AFTER SHOWING COMPLIANCE WITH STC AND ICC,
 CONSIDERATION CAN BE GIVEN TO APPLYING THIS EXCEPTION
 TO THE FLAME SPREAD REQUIREMENT IF THE PRODUCT DOES NOT
 ALREADY HAVE A FLAME SPREAD TEST.
  
 STC AND IIC TEST REPORTS ARE REQUIRED. DUE TO THE
 INCONSISTENCIES IN MANUFACTURERS' SPEC SHEETS, PERMITS
 ARE NOT ISSUED BASED ON THE SPEC SHEETS. YOU MAY SEND
 THE TEST REPORTS VIA EMAIL FOR PRELIMINARY REVIEW.
 PRIOR TO SENDING THE TEST REPORTS, CONFIRM THAT THE
 ASSEMBLY TESTED DID NOT INCLUDE A DROPPED GYPSUM
 CEILING. AN ANALYSIS MAY BE REQUIRED FOR HOLLOW CORE AS
 I'VE NEVER SEEN A PRODUCT TESTED WITH A HOLLOW CORE
 FLOOR, ONLY CONCRETE SLABS.
  
 NEW COMMENT:
  
 7. A CODE SUMMARY WAS ADDED TO SHEET A2.4B; CLUBHOUSE
 OCCUPANCY CLASSIFICATION IS DECLARED AS B. THIS SHOULD
 BE MIXED OCCUPANCY; CLUBHOUSE IS ASSEMBLY OCCUPANCY
 (PROBABLY A3), REVISE.
  
 THE PLAN CAN BE REDLINED UPON REQUEST.
  
 PLAN HAVE BEEN STAMPED AS APPROVED. THE FLOORING
 UNDERLAYMENT ISSUE AND VALUE CAN BE RESOLVED VIA EMAIL.
 THE SOFFIT PRODUCT APPROVAL CAN BE PROVISO ITEM UPON
 REQUEST.
  
 *****************************************
 16111261 BLDG 1 (NORTH)
 16111265 BLDG 2
 16111259 CLUBHOUSE
  
 16111261 BUILDING DATA FOR C.O./REPORTING
 USC-404 TYPE 434 - ALT RESIDENTIAL
 SQUARE FEET - 69509
  
 CONSTRUCTION TYPE: 14-2-B
 UNITS:
 FLOORS: 4
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 69509
 SQ FT FOOTPRINT: 18480
 SQ FT ROOF: 18480
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
  