| 2017-06-28 12:56:46 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1-2. OK |
| | |
| | 3. FROM PREVIOUS LISTS: KAYKAN SOFFIT PRODUCT APPROVAL, |
| | INDICATE WHICH PRODUCT AND INSTALLATION METHOD IS |
| | PROPOSED (DRAWING PAGE 1 OF 15). |
| | |
| | 2ND REVIEW, THE DOCUMENT SUBMITTED IS NOT A PART OF THE |
| | PRODUCT APPROVAL. IT APPEARS TO BE AN EVALUATION REPORT |
| | BUT DOES NOT INCLUDE A PRODUCT APPROVAL NUMBER. ONE |
| | ITEM IS CIRCLED, 20' MRH, BUT THE APARTMENT BUILDINGS |
| | ARE FOUR STORIES. |
| | |
| | THIS ITEM CAN BE A PROVISO UPON REQUEST - PRIOR TO |
| | INSTALLATION, SUBMIT PRODUCT APPROVAL WITH INSTALLATION |
| | METHOD INDICATED. |
| | |
| | 3RD REVIEW, RESPONSE LETTER STATES THAT IT IS ATTACHED, |
| | BUT I WAS UNABLE TO LOCATE THIS INFORMATION. |
| | |
| | 4. OK |
| | |
| | 5. WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR |
| | THIS JOB, FBC 105. |
| | |
| | 6. TEST REPORTS FOR THE FLOORING UNDERLAYMENT WERE NOT |
| | PROVIDED. "GROUNDWORKS" SPEC SHEET WAS PROVIDED. |
| | |
| | PROVIDE TEST REPORTS FOR THE FLOORING UNDERLAYMENT |
| | ACOUSTIC INSULATION: |
| | |
| | A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | |
| | B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | C. FBC B 720.2 OR 603.1, PROVIDE TEST DATA IN |
| | ACCORDANCE WITH ASTM E 84 OR UL 723 (FLAME SPREAD). |
| | |
| | 3RD REVIEW, RESPONSE LETTER REFERS TO AN EXCEPTION FOR |
| | COMBUSTIBLE INSULATION BOARDS NOT MORE THAN 1/2"; IT |
| | APPEARS THAT THE PROPOSED PRODUCT IS A ROLLED PRODUCT, |
| | NOT BOARDS. AFTER SHOWING COMPLIANCE WITH STC AND ICC, |
| | CONSIDERATION CAN BE GIVEN TO APPLYING THIS EXCEPTION |
| | TO THE FLAME SPREAD REQUIREMENT IF THE PRODUCT DOES NOT |
| | ALREADY HAVE A FLAME SPREAD TEST. |
| | |
| | STC AND IIC TEST REPORTS ARE REQUIRED. DUE TO THE |
| | INCONSISTENCIES IN MANUFACTURERS' SPEC SHEETS, PERMITS |
| | ARE NOT ISSUED BASED ON THE SPEC SHEETS. YOU MAY SEND |
| | THE TEST REPORTS VIA EMAIL FOR PRELIMINARY REVIEW. |
| | PRIOR TO SENDING THE TEST REPORTS, CONFIRM THAT THE |
| | ASSEMBLY TESTED DID NOT INCLUDE A DROPPED GYPSUM |
| | CEILING. AN ANALYSIS MAY BE REQUIRED FOR HOLLOW CORE AS |
| | I'VE NEVER SEEN A PRODUCT TESTED WITH A HOLLOW CORE |
| | FLOOR, ONLY CONCRETE SLABS. |
| | |
| | NEW COMMENT: |
| | |
| | 7. A CODE SUMMARY WAS ADDED TO SHEET A2.4B; CLUBHOUSE |
| | OCCUPANCY CLASSIFICATION IS DECLARED AS B. THIS SHOULD |
| | BE MIXED OCCUPANCY; CLUBHOUSE IS ASSEMBLY OCCUPANCY |
| | (PROBABLY A3), REVISE. |
| | |
| | THE PLAN CAN BE REDLINED UPON REQUEST. |
| | |
| | PLAN HAVE BEEN STAMPED AS APPROVED. THE FLOORING |
| | UNDERLAYMENT ISSUE AND VALUE CAN BE RESOLVED VIA EMAIL. |
| | THE SOFFIT PRODUCT APPROVAL CAN BE PROVISO ITEM UPON |
| | REQUEST. |
| | |
| | ***************************************** |
| | 16111261 BLDG 1 (NORTH) |
| | 16111265 BLDG 2 |
| | 16111259 CLUBHOUSE |
| | |
| | 16111261 BUILDING DATA FOR C.O./REPORTING |
| | USC-404 TYPE 434 - ALT RESIDENTIAL |
| | SQUARE FEET - 69509 |
| | |
| | CONSTRUCTION TYPE: 14-2-B |
| | UNITS: |
| | FLOORS: 4 |
| | BEDROOMS: |
| | ROOMS: |
| | SQ FT LIVABLE: 69509 |
| | SQ FT FOOTPRINT: 18480 |
| | SQ FT ROOF: 18480 |
| | |
| | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF |
| | KNOWN): |
| | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): |
| | XX.XX |
| | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: |
| | XX.XX |
| | OCC LOAD: |
| | PROP USE: APARTMENT |
| | SPRINKLER SYS? Y |
| | SPRK REQ'D? Y |
| | BATHRMS: |
| | |
| | BLDG CODE: FL 2014 |
| | OCC CLASS: 5TH ED R-2 |
| | |