Plan Review Notes
Plan Review Notes For Permit 16111261
Permit Number 16111261
Review Stop M
Sequence Number 2
Notes
Date Text
2017-03-29 10:10:282ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16111261
 3/29/17
  
 1) ENERGY COMPLIANCE: DUPLICATE COPIES OF THE SUBMITTED
 ENERGY COMPLIANCE FORM C402-2014 ARE REQUIRED FOR BOTH
 BUILDINGS #1 & 2. ONLY TWO FORMS WERE SUBMITTED AND NO
 BUILDING NUMBERS ARE SHOWN ON THE FORMS.
  
 2) SHEET M2.2: THERE IS A RETURN TRANSFER MISSING IN
 THE MIDDLE BEDROOM OF THE 2-BEDROOM UFAS UNIT.
  
 3) SHEET M3.2: INDICATE THE NUMBER OF CLIPS TO BE
 INSTALLED ON THE CONDENSER UNITS. PROVIDE TWO COPIES OF
 FL. PRODUCT APPROVAL #19731 WITH A SHOP DRAWING
 APPROVAL STAMP BY THE ARCHITECT OF RECORD. THE
 ARCHITECT MUST ALSO CIRCLE, HIGHLIGHT, OR OTHERWISE
 MARK ALL APPLICABLE ANCHORING DETAILS, NOTES, DESIGN
 PRESSURES ETC. ON THE PRODUCT APPROVAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER