2017-03-28 15:56:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1-2. OK
  
 3. FROM PREVIOUS LIST: KAYKAN SOFFIT PRODUCT APPROVAL,
 INDICATE WHICH PRODUCT AND INSTALLATION METHOD IS
 PROPOSED (DRAWING PAGE 1 OF 15).
  
 2ND REVIEW, THE DOCUMENT SUBMITTED IS NOT A PART OF THE
 PRODUCT APPROVAL. IT APPEARS TO BE AN EVALUATION REPORT
 BUT DOES NOT INCLUDE A PRODUCT APPROVAL NUMBER. ONE
 ITEM IS CIRCLED, 20' MRH, BUT THE APARTMENT BUILDINGS
 ARE FOUR STORIES.
  
 THIS ITEM CAN BE A PROVISO UPON REQUEST - PRIOR TO
 INSTALLATION, SUBMIT PRODUCT APPROVAL WITH INSTALLATION
 METHOD INDICATED.
  
 4. OK
  
 5. WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR
 THIS JOB, FBC 105.
  
 6. TEST REPORTS FOR THE FLOORING UNDERLAYMENT WERE NOT
 PROVIDED. "BRAVO UNDERLAYMENT" SPEC SHEET WAS PROVIDED.
  
 PROVIDE TEST REPORTS FOR THE FLOORING UNDERLAYMENT
 ACOUSTIC INSULATION:
  
 A. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 B. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC B 720.2 OR 603.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723 (FLAME SPREAD).
  
 7. BUILDING TYPE (SHEET G0.1) IS IIIB. REVISE PLAN TO
 INCLUDE THE FLOOR CEILING ASSEMBLY; THIS INFORMATION IS
 REQUIRED TO DETERMINE COMPLIANCE FOR THE FLOORING
 UNDERLAYMENT SELECTED.
  
 RESPONSE LETTER STATES THAT THIS IS HOLLOW CORE PLANK,
 BUT THE PLAN WAS NOT REVISED. THIS CAN BE A PROVISO
 ITEM UPON REQUEST. RESPONSE LETTERS ARE HELPFUL FOR
 REVIEW BUT NOT SIGNED AND SEALED, ARE NOT RETAINED, ARE
 NOT A PART OF THE PERMIT RECORD.
  
 8-10. OK
  
 NEW COMMENT:
  
 11. FIRE RATED WINDOWS ARE SPECIFIED. THIS PERMIT WILL
 BE ISSUED WITH PROVISO, PRODUCT APPROVAL FOR THE WINDOW
 AND IMPACT PROTECTION TO BE SUBMITTED PRIOR TO
 INSTALLATION. INSTALLATION METHOD TO BE MARKED ON THE
 IMPACT PROTECTION PRODUCT APPROVAL. A SHUTTER
 INSTALLATION PLAN IS ALSO REQUIRED; WHO WILL DO THE
 INSTALLATION, WHERE THE IMPACT PROTECTION WILL BE
 STORED IF REMOVABLE IMPACT PROTECTION IS PROPOSED, HOW
 IT WILL BE INSTALLED ON A FOUR STORY BUILDING.
  
 WHEN A FIRE RATED WINDOW IS REQUIRED, RATED GLASS BLOCK
 IS OFTEN USED AS THERE IS NO IMPACT REQUIREMENT IN
 NON-HVHZ.
  
  