| 2016-12-07 11:15:08 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16111261 | | | 12/7/16 | | | | | | 1) THE RESIDENTIAL ENERGY COMPLIANCE FORM R405-2015 | | | CANNOT BE USED ON A COMMERCIAL BUILDING. PLEASE SEE | | | DEFINITIONS OF RESIDIENTIAL AND COMMERCIAL IN SECTIONS | | | C202 & R202 FBC-14 ENERGY CONSERVATION. RESIDENTIAL | | | CLASSIDICATION IS LIMITED TO THREE STORIES. THE | | | BUILDING BEING RENOVATED IS FOUR STORIES. | | | | | | 2) SUBMIT AC CHANGEOUT FORMS FOR THE REPLACED SYSTEMS. | | | THE FORMS CAN BE FOUND ON THE DEVELOPMENT SERVICES | | | WEBSITE- WWW.CITYOFWPB.COM. | | | | | | 3) SHEET M2.3: THE 8X6 TRANSFER DUCTS IN THE | | | THREE-BEDROOM UNITS ARE UNDERSIZED PER SECTION | | | 601.5.(1). | | | | | | 4) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR | | | ANCHORING THE NEW CONDENSER UNITS TO THE EXISTING ROOF | | | STANDS- SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|