| 2017-01-04 15:35:12 | JOB PERMIT NUMBER: 16111261 |
| | JOB ADDRESS: 2100 NORTH AUSTRALIAN AVE |
| | WEST PALM BEACH FLORIDA |
| | DATE: JANUARY 4, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] FIRE ALARM, LOW VOLTAGE, & SITE LIGHTING SHALL BE |
| | SUBMITTED UNDER A SEPARATE PERMIT WITH SEPARATE SHOP |
| | DRAWINGS. |
| | |
| | 2] A MINIMUM OF 75% OF PERMANENTLY INSTALLED LUMINAIRES |
| | SHALL BE HIGH EFFICIENT & RECESSED LIGHTS INSTALLED IN |
| | BUILDING THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR |
| | LEAKAGE BETWEEN CONDITIONED & UN-CONDITIONED SPACES, |
| | THE HOUSING CANS IF IN CONTACT WITH THERMAL INSULATION |
| | SHALL BE LISTED IC-RATED. FBC-ENERGY SECTIONS R402.4.4 |
| | & R404.1 (ADD A NOTE ON SHEET E0.1) |
| | |
| | 3] OPENINGS AROUND ELECTRICAL PENETRATIONS INTO OR |
| | THROUGH FIRE RESISTANT WALLS, PARTITIONS, FLOORS, & |
| | CEILINGS SHALL BE FIRE STOPPED USING APPROVED METHODS |
| | TO MAINTAIN THE FIRE RATING. NEC 300.21 THIS APPLIES TO |
| | HALLWAY CORRIDORS IN SHEETS E1.1, E1.2, E1.3. (ADD A |
| | NOTE) |
| | |
| | 4] DEPENDING ON CONDUIT ROUTING PLEASE REFERENCE NEC |
| | 310.15 FOR TEMPERATURE ADJUSTMENT & CORRECTIONS FOR |
| | CONDUCTORS BEING RAN ON THE ROOFTOP EXPOSED TO DIRECT |
| | SUNLIGHT. ADD A NOTE ON SHEET E1.4. |
| | |
| | 5] PROVIDE AFCI PROTECTION TO NEW OR MODIFIED CIRCUITS |
| | IN ACCORDANCE WITH NEC 210.12(A)(B). ADD A NOTE ON |
| | SHEET E2.1, E2.2, E2.3. |
| | |
| | 6] PROVIDE ILLUMINATION FOR THE PANELBOARD ON BEDROOM 1 |
| | PER NEC 110.26(D). |
| | |
| | 7] CLARIFY IF DISTRIBUTION PANELS ARE ACCESSIBLE TO |
| | TENANT'S OR IS THEIR MAINTENANCE PERSONNEL WITH KEY |
| | LOCK ACCESS IN ACCORDANCE WITH NEC 240.24(B). |
| | |
| | 8] PROVIDE EMERGENCY LIGHTING IN MEN'S/WOMAN'S BATHROOM |
| | & MECHANICAL ROOM FOR MEANS OF EGRESS ILLUMINATION PER |
| | FBC 1006. |
| | |
| | 9] SHOW IDENTIFICATION ON THE RISER DIAGRAM OF UNIT #'S |
| | ON THE MAIN DISCONNECTS & THE DISTRIBUTION PANELS SHALL |
| | HAVE THE SOURCE OF SUPPLY MARKING PER NEC 225.37, |
| | 408.4(B). |
| | |
| | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |