2017-01-04 15:35:12JOB PERMIT NUMBER: 16111261
 JOB ADDRESS: 2100 NORTH AUSTRALIAN AVE
 WEST PALM BEACH FLORIDA
 DATE: JANUARY 4, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] FIRE ALARM, LOW VOLTAGE, & SITE LIGHTING SHALL BE
 SUBMITTED UNDER A SEPARATE PERMIT WITH SEPARATE SHOP
 DRAWINGS.
  
 2] A MINIMUM OF 75% OF PERMANENTLY INSTALLED LUMINAIRES
 SHALL BE HIGH EFFICIENT & RECESSED LIGHTS INSTALLED IN
 BUILDING THERMAL ENVELOPE SHALL BE SEALED TO LIMIT AIR
 LEAKAGE BETWEEN CONDITIONED & UN-CONDITIONED SPACES,
 THE HOUSING CANS IF IN CONTACT WITH THERMAL INSULATION
 SHALL BE LISTED IC-RATED. FBC-ENERGY SECTIONS R402.4.4
 & R404.1 (ADD A NOTE ON SHEET E0.1)
  
 3] OPENINGS AROUND ELECTRICAL PENETRATIONS INTO OR
 THROUGH FIRE RESISTANT WALLS, PARTITIONS, FLOORS, &
 CEILINGS SHALL BE FIRE STOPPED USING APPROVED METHODS
 TO MAINTAIN THE FIRE RATING. NEC 300.21 THIS APPLIES TO
 HALLWAY CORRIDORS IN SHEETS E1.1, E1.2, E1.3. (ADD A
 NOTE)
  
 4] DEPENDING ON CONDUIT ROUTING PLEASE REFERENCE NEC
 310.15 FOR TEMPERATURE ADJUSTMENT & CORRECTIONS FOR
 CONDUCTORS BEING RAN ON THE ROOFTOP EXPOSED TO DIRECT
 SUNLIGHT. ADD A NOTE ON SHEET E1.4.
  
 5] PROVIDE AFCI PROTECTION TO NEW OR MODIFIED CIRCUITS
 IN ACCORDANCE WITH NEC 210.12(A)(B). ADD A NOTE ON
 SHEET E2.1, E2.2, E2.3.
  
 6] PROVIDE ILLUMINATION FOR THE PANELBOARD ON BEDROOM 1
 PER NEC 110.26(D).
  
 7] CLARIFY IF DISTRIBUTION PANELS ARE ACCESSIBLE TO
 TENANT'S OR IS THEIR MAINTENANCE PERSONNEL WITH KEY
 LOCK ACCESS IN ACCORDANCE WITH NEC 240.24(B).
  
 8] PROVIDE EMERGENCY LIGHTING IN MEN'S/WOMAN'S BATHROOM
 & MECHANICAL ROOM FOR MEANS OF EGRESS ILLUMINATION PER
 FBC 1006.
  
 9] SHOW IDENTIFICATION ON THE RISER DIAGRAM OF UNIT #'S
 ON THE MAIN DISCONNECTS & THE DISTRIBUTION PANELS SHALL
 HAVE THE SOURCE OF SUPPLY MARKING PER NEC 225.37,
 408.4(B).
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER